RA Range Installation Instructions

Stage 1 – INSTALLATION

Stage 2 – ADJUSTMENT

Nail here

Nail here

Ensure return flange abuts masonry

— Ensure joists just fit between the walls — If using I–joists and they are too long, trim to fit — Position joist against location tab — Pre–fix RA to each end of pre–cut joist, nailing through slotted holes in base plate and side flange only, as shown — Slide to opposite side of slots to provide full 6mm adjustment on wall head — Always pre–fix hangers at ground level or on scaffolding

— Locate assembled joist on wall head allowing equal adjustment at both ends — Adjust each end by tapping with a hammer until return flange is correctly positioned tight against blockwork — This stage provides a maximum horizontal adjustment of 12mm and suits blockwork built to BS5606:1990 Accuracy in Building

Ensure return flange abuts masonry

Stage 3 – FINAL ADJUSTMENT

DECKING INSTALLATION FOR FLOORS

150mm min

10mm expansion gap

Minimum edge distance for decking nails = 150mm

— Fully nail using 3.4 x 35mm square twist nails

DO NOT apply any load to joist prior to RA being fully nailed