Cullen Technical Guide 2024

/

VRC Variable Ridge Connector

Load Data

Characteristic Capacity (kN)

Hanger Depth (mm)

Dimensions (mm)

Fixings (3.4x35mm)

Angles

Header Specification

Uplift

Solid Timber (Min TR26), Glulam (Min GL28h), LVL & I–Joist (1)

(Depth Dependant Only)

H

Header

Incoming

Slope

Skew

Oº Oº

n/a (90º)

2.59 2.59 2.59 2.59 2.59 2.59 2.59 2.59

6.85 6.40

30º to 87.5º

195

190

9

8

(–35º to +45º) (–35º to +45º)

n/a (90º)

10.20

30º to 87.5º

8.54 6.85 6.40

0º 0º

n/a (90º)

30º to 87.5º

350

345

12

8

(–35º to +45º) (–35º to +45º)

n/a (90º)

10.20

30º to 87.5º

8.54

(1) I–Joist headers require backer blocks to be installed as per joist manufacturer’s instructions.

Installation Instructions Stage 1

Stage 2

Stage 3

+45

0

-35

Face fix VRC to solid header using 9No 3.4 x 35mm square twist nails. Adjust angle of base plate if slope is required.

Offer incoming member and fix using 2No 3.4 x 35mm square twist nails to the underside of the incoming member.

Wipe up the bottom side flange at the appropriate crease line and fill the 2No nail holes closest to the bend line with 3.4 x 35mm square twist nails.

Stage 4

Stage 5 (For skewed applications only)

Right hand version

Left hand version

Wipe round the top side flange at the appropriate crease line and fill all the nail holes into the incoming joist. Minimum 4No 3.4 x 35mm square twist nails.

Rotate hanger to angle required. Correct hand must be used. Please ensure the correct hanger has been selected prior to installing.

The latest most up to date version will always be online and not in print or in downloaded pdf.

84

Technical support 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk