Cullen Technical Guide 2024

/

UZ CLIP

NEW Additional Application

Noggin Support with Buttress Wall

In Situ

No. of UZ Clips

Characteristic Value (kN) (Horizontal Direction)

Noggin Size (mm)

38 × 63 to 38 × 89

2

1.5

38 × 120

4

2.5

*Values are of partition positioned anywhere on the noggin.

Buttress Wall to Noggin Bottom rail is secured to the noggin through the floorboard using a PSTS–8x85mm screw.

Buttress Wall

Buttress Wall

Noggins are evenly spaced between the joists (excluding perimeter noggin) and installed using UZ clips.

Buttress wall can be positioned off–centre on the noggins.

Example Calculation 1no. Noggin minimum 38×63mm fixed with 2no.UZ–clips (1 each end) Instantaneous design value (Wind kmod 1.1) for noggin (centre or end) = 1.269kN Instantaneous design value (Wind kmod 1.1) for Screw fixing PSTS8x85mm (assume panel has 38mm bottom member = 1.684kN Buttress wall with 4 noggins maximum loading 1.269* × 4 = 5.076kN

1no. Noggin minimum 38×120mm fixed with 4no.UZ–clips (2 each end) Instantaneous design value (Wind kmod 1.1) for noggin (centre or end) = 2.115kN Instantaneous design value (Wind kmod 1.1) for Screw fixing PSTS8x85mm (assume panel has 38mm bottom member = 1.684kN Buttress wall with 4 noggins maximum loading 1.684* × 4 = 6.736kN

*Lowest Value of clip/screw used for calculation

The latest most up to date version will always be online and not in print or in downloaded pdf.

89

Technical support 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk

Made with FlippingBook Annual report maker