PAPERmaking! Vol5 Nr2 2019

WEEK 1 (2, 3, 4 ….)

Date

Time

Print Name

Circle as required

Result of evaporation test

Boiler One

Boiler Two

Boiler Three

Gauge glasses blown down

No

No

No

Yes

Yes

Yes

Failed

Failed

Failed

1 st low audible alarm

Sounded

Sounded

Sounded

Failed

Failed

Failed

1 st low visual alarm

Observed

Observed

Observed

Burner shutdown at 1 st low

Failed

Failed

Failed

Yes

Yes

Yes

Failed

Failed

Failed

2 nd low audible alarm Sounded

Sounded

Sounded

Failed

Failed

Failed

2 nd low visual alarm

Observed

Observed

Observed

Boiler lock out at 2 nd low Remote alarm (audible) Security Lodge Remote alarm (visual) Security Lodge Is water visible in gauge glasses at lockout? Pump on after 1 st low recovered

Failed

Failed

Failed

Yes

Yes

Yes

Failed

Failed

Failed

Sounded

Sounded

Sounded

Failed

Failed

Failed

Observed

Observed

Observed

Failed

Failed

Failed

Yes

Yes

Yes

Failed

Failed

Failed

Yes

Yes

Yes

Failed

Failed

Failed

Burner restart check

Normal

Normal

Normal

Flame Inspection at Low Fire Hold

Normal

Abnormal

Normal

Abnormal

Normal

Abnormal

Pump stop and start

Normal

Abnormal

Normal

Abnormal

Normal

Abnormal

Flame failure device test Manual blow down performed

Failed

Failed

Failed

Passed

Passed

Passed

Not performed Not confirmed

Not performed Not confirmed

Not performed

Performed

Performed

Performed

Blow down OK Not confirmed IN THE EVENT OF ANY FAILURE OF EITHER THE EVAPORATION TEST OR THE FLAME FAILURE DEVICE, THE BOILER IS TO BE SHUT DOWN AND ISOLATED. THE FAILURE MUST BE REPORTED AND RECORDED IMMEDIATELY. Confirmed Confirmed Confirmed

BG01 Guidance on the safe Operation of Steam Boilers Edition 2 – © 2019