Case study 2: Biofuel plant gensets

A biofuel plant, based in the UK, installed a double water vessel heat exchanger to recover energy from its gensets. The Spirax Sarco solution was a bespoke design of an irregular shape, to take account of the large duct diameter, which necessitated a large cross sectional area on the unit. The application recovered 750 KW of energy with a value of £175,000 per annum. The payback on this application for the customer was less than six months.

Exhaust temperature in / out Water temperature in / out ([KDXVWZDWHUPDVVÀRZ

440°C / 371°C

75°C / 98°C

46,500kg/h / 36,210kg/h

Weight of unit

1,556kg 850Pa 750kW

Exhaust pressure drop

Energy recovered

Recovered energy value

£175k p/a

Case study 3: Gas to water food processing boiler

6PRRWKSLSHKHDWH[FKDQJHU¿WWHGWRDIRRGSURFHVVLQJERLOHU The application suffered from high particulate matter exhaust from the furnace. The Spirax Sarco solution was to install a gas-to-water heat pipe heat exchanger, with a soot trap and removable panels for easy cleaning. The company now has a low fouling, low maintenance, high reliability heat exchanger capable of recovering £82,000 of energy per annum for a capital investment of £40,000, offering a payback period of less than a year.

Exhaust temperature in / out Water temperature in / out ([KDXVWZDWHUPDVVÀRZ

236°C / 158°C 105°C / 131°C

18,675kg/h / 6,374kg/h

Weight of unit

3,600kg 650Pa 440kW £82k p/a

Exhaust pressure drop

Energy recovered

Recovered energy value