directly to the pump (such as Grundfos dielectric isolation valves). The following picture shows a pump that is dielectrically isolated from the GARN® unit:

A simple solution to isolate the controller is to remove the controller from its steel stud mounting, screw a piece of plywood into the steel studs, then mount the controller to the plywood. Make sure the controller mounting screws are not in contact with the steel studs. Plywood is an effective electric isolator. 6. Isolation is now complete, and the schematic of how the installation should look is:

By installing dieletric unions (or equivalent) on or near the Hot Water Supply (HWS) and Hot Water Return (HWR) connections of the GARN® unit, electric isolation is achieved for any and all components connected downstream.

5. Isolate the controller:

In some installations, the controller may be directly screwed into steel studs. The steel studs may then be in direct contact with the GARN® unit. In such a situation, the housing of the controller is effectively a ground path to the tank.

The GARN® unit is now fully electrically isolated. Anode rods are not needed. If the installation changes over time and other electrical devices are installed on or near the GARN® unit that are wired to ground, keep these concepts in mind and isolate appropriately.

81

GARN® WHS 1000 and WHS 2000 Manual | © HY-C® Company LLC | October 2024