Unistrut P1001
41
A
= 6.70 cm 2 /m = 5.77 kg/m
I y-y = 36.27 cm 4 Z y-y = 8.78 cm 3 r y-y = 2.32 cm I z-z = 18.46 cm 4 Z z-z = 8.94 cm 3 r z-z = 1.66 cm
83
P1001
2,5mm
PO
HG
PG
SS
F
L (mm)
Continuously Seam Welded
f= 1 /
f=
1 /
σ =175 N/mm 2
200 L
360 L
HG
F (kN)
f
F max(kN)
F (kN)
F (kN)
f max(mm)
Spot Welded
SS
250 500 750
- -
- -
- - - - - - - - -
- - - - -
28.253 28.096 27.792 27.301 26.438 25.025 23.220 21.288 19.394 17.619 15.990 14.519*
16.383 12.292 9.830 8.191 7.024 6.141 5.454 4.915 4.464 4.091
1.21 2.15 3.36 4.84 6.59 8.61
1000 1250 1500 1750 2000 2250 2500 2750 3000
7.044 5.170 3.963 3.129 2.531 2.090 1.756
10.89 13.45 16.27 19.37
4.562 3.767 3.169
*180 ≤ kL/r < 250
41
T = 14 x 28 mm
A
= 6.00 cm 2 /m = 5.47 kg/m
I y-y = 36.21 cm 4 Z y-y = 8.77 cm 3 r y-y = 2.45 cm I z-z = 18.34 cm 4 Z z-z = 8.88 cm 3 r z-z = 1.74 cm
83
P1001T
2,5mm
PO
HG
PG
SS
F
L (mm)
f= 1 /
f=
1 /
Continuously Seam Welded
σ =175 N/mm 2
200 L
360 L
HG
F (kN)
f
F max(kN)
F (kN)
F (kN)
f max(mm)
250 500 750
- -
- -
- - - - - - - - -
- - - - -
27.458 27.311 27.027 26.585 25.830 24.584 22.906 21.042 19.198 17.452 15.8520 14.391*
Spot Welded
PO PG SS
16.363 12.272 9.820 8.182 7.014 6.131 5.454 4.905 4.464 4.091
1.21 2.15 3.36 4.84 6.59 8.61
1000 1250 1500 1750 2000 2250 2500 2750 3000
7.034 5.170 3.953 3.120 2.531 2.090 1.756
10.90 13.46 16.28 19.38
4.552 3.767 3.159
*180 ≤ kL/r < 250
Part No.
Length M
Finish
Slot Size (T)
3
6
PO
PG
HG
SS
25x11
28x14
• Allied Tube & Conduit •
Stated loadings apply to mild steel products only.
• • •
• • •
• • •
• • •
• • •
• • •
P1001
P1001T
P1001T10
16
Made with FlippingBook Digital Publishing Software