Gable Restraint System Technical Guide UP TO 5 STOREYS
Gable Restraint System
ITW Construction Products’ Cullen brand of timber engineering connectors has been synonymous with innovation and quality for over forty years. In collaboration with national housebuilders, the Trussed Rafter Association and industry partners, ITWs technical experts have created an innovative system featuring the Cullen Gable Restraint Bracket for a complete
on the masonry and timber gable ends into the braced roof diaphragm. This provides a verified connection between timber gable panels to masonry walls. The details give an option to have a continuous wall plate or a stepped wallplate with the gable wall plate being raised to suit the bottom chord depth of the truss. Either of the details meets the requirement of Building Regulations 2010 approved document A, Scottish Building regulations domestic, NHBC Standards for houses
of five storeys or less in England and Wales and four storeys or less in Scotland. Both details are accepted by NHBC. This NHBC accepted “whole system” solution incorporating the Cullen Gable Restraint Bracket and restraint straps including Paslode nail fixings with all centres, spacings and connections already calculated means that whenever our detail is followed the system is underwritten by ITW Construction Products.
solution to connect timber gables to masonry walls.
The details have been developed to safely transfer lateral wind load
Please note the GRB forms part of a system and must be used in conjunction with the system straps and fixings as shown below.
The Gable Restraint System is comprised of the following specified products:
GRB-100
VRS-900-100
Patent Pending
Establishes a verified connection between a timber gable and a masonry wall.
Provides a secure method of fixing wall plates to timber and masonry walls.
RST-3
PFS-1500-100-B
FT: The Timber Frame Wall Tie
A high-performance strap developed to resist uplift and provide lateral restraint for timber gables.
Delivers superior performance and exceptional flexibility, ideal for lateral restraint in floor and roof applications.
Restrains the external blockwork or brickwork back to the timber frame structure.
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 2
Gable Restraint Bracket & Application
Gable panel Timber wallplate Mortar bed
Gable restraint bracket
Masonry wall
Gable Restraint Bracket Installation
Components: – Wallplate – Mortar – Gable Restraint Brackets – Wall
Gable restraint brackets placed on wall at 1200mm* maximum centres (no fixings required). *for buildings up to 3 storey England & Wales and 2 storey Scotland
10mm maximum mortar bed on wall prior to wallplate being fixed.
38-75mm wallplate bedded on mortar and fixed to gable restraint brackets with 3.5x40mm wood screws (2 no. per bracket).
Gable Restraint Bracket Installation Video
Scan or click to view installation videos
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 3
Gable Restraint System
Class 1 Buildings / houses of single occupancy three storeys or less England & Wales and two storeys or less Scotland Timber Gable to Masonry fixing detail to cold roofs – continuous wallplate
Gable Panel
225mm maximum height between underside of wallplate and horizontal restraint strap
Insulation continued into gable panel
Breather membrane to face of gable panel
Roof insulation
Cullen FT Timber frame wall ties
Longitudinal truss bracing
Continuous wallplate 38mm min-75mm maximum depth
Level of truss wallplate
Solid blocking between truss and gable panel at horizontal restraint strap positions Gable panel to wallplate fixing - Paslode 3.1mm dia x min 75mm long smooth shank nails at maximum 175mm centres Vertical holding down strap plugged and screwed to blockwork
Mortar bed
Cullen RST-3 restraint straps at maximum 1200mm centre fixed to longitudinal truss bracing /
Cullen Gable Restraint Bracket (GRB) at maximum 1200mm centres
additional longitudinal bracing with 8 no. 4 x 25mm steel screws fixed to gable panel stud with 3 no. 3.4 x 35 mm square twist nails
Cavity insulation shown for indicative purposes only - thermal bridging and SAP calculations are plot specific Cavity trays and firestops to be detailed by building designer
at maximum 1.8m centres, Cullen VRS-900-100 strap
Gable Panel (without gable ladder)
Cullen PFS restraint straps fixed to solid timber noggins between trusses at maximum 2000mm centres with 3.4 x 35mm square twist nails, 8 no. to noggins and 4 no. to gable panel (2 no. top face & 2 no. cavity face)
Cullen RST-3 restraint straps at maximum 1200mm centres fixed to additional longitudinal bracing with 8 no. 4 x 25mm steel screws fixed to gable panel stud with 3 no. 3.4 x 35mm square twist nails
Gable Panel (with or without gable ladder)
Truss profile
Bottom rail of gable panel
Continuous wallplate 38mm min-75mm maximum depth
1200mm max
Mortar bed
1200mm max
1200mm max
1200mm max
Cullen Gable Restraint Bracket (GRB) at maximum 1200mm centres
Cullen VRS-900-100 fixed to top of bottom rail with 4 no. 3.4 x 35mm square twist nails
1800mm maximum
Vertical restraint strap plugged and screwed to blockwork at maximum 1.8m centres - Cullen VRS-900-100 installed to top of gable panel bottom rail
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 4
Class 1 Buildings / houses of single occupancy three storeys or less England & Wales and two storeys or less Scotland
Timber Gable to Masonry fixing detail to cold roofs – raised gable wallplate Cavity trays and firestops to be detailed by building designer Gable Panel
Breather membrane to face of gable panel
Insulation continued into gable panel
Cullen FT Timber frame wall ties Wallplate 38mm min- 75mm maximum depth
Roof insulation
Longitudinal truss bracing (depth can vary to suit blockwork level)
Mortar bed
Level of truss wallplate
Levels to be adjusted to ensure top of bracing inline with top of blockwork Cullen Gable Restraint Bracket (GRB) at maximum 1200mm centres Cavity insulation shown for indicative purposes only - thermal bridging and SAP calculations to be plot specific
Solid blocking between truss and gable panel at horizontal restraint strap positions Gable Panel to wallplate fixing - Paslode 3.1mm dia x min 75mm long smooth shank nails at maximum 175mm centres Vertical holding down strap plugged and screwed to blockwork at maximum 1.8m centres Cullen VRS-900-100 strap
Cullen PFS-1500-100-B restraint straps at maximum 2000mm centre fixed to longitudinal truss bracing / additional longitudinal bracing with 8no. 4x25mm steel screws fixed to gable panel stud with 3no. 3.4x35mm square twist nails
Gable Panel (with or without gable ladder)
Cullen PFS restraint straps fixed to solid timber noggins between trusses at maximum 2000mm centres with 3.4 x 35mm square twist nails, 8 no. to noggins and 4 no. to gable panel (2 no. top face & 2 no. cavity face)
Gable Panel (without gable ladder)
Truss profile
Bottom rail of gable panel
Cullen VRS-900-100 fixed to top of bottom rail with 4 no. 3.4 x 35mm square twist nails Cullen PFS restraint straps bedded in mortar joint between top of masonry and wallplate and fixed to longitudinal truss bracing maximum 2000mm centres with 8 no. 4 x 25mm steel screws
Continuous wallplate 38mm min-75mm maximum depth
2000mm max
Mortar bed
1200mm max
1200mm max
1200mm max
Cullen Gable Restraint Bracket (GRB) at maximum 1200mm centres
1800mm maximum
Vertical restraint strap plugged and screwed to blockwork at maximum 1.8m centres - Cullen VRS-900-100 installed to top of gable panel bottom rail
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 5
Gable Restraint System
Class 1 Buildings / houses of single occupancy three storeys or less England & Wales and two storeys or less Scotland Openings within gable walls
When GRB & VRS restraint straps clash with opening positions and cavity trays above openings please position to suit the following – these details can be applied to continuous & raised wallplate.
Repositioned / additional GRB to be kept back from opening to avoid clashing with cavity tray.
3600mm maximum
300mm min
300mm min
150mm min
150mm min
1200mm max
1200mm max
1200mm max
2400mm maximum opening width
300mm min
300mm min
1800mm maximum
3600mm maximum
1800mm maximum
1800mm maximum
Repositioned / additional VRS holding down strap either side of opening.
Where large door / window openings GRB’s / VRS restraint straps to be repositioned / additional installed either side of the opening with maximum and minimum centres shown above.
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 6
Timber Gable to Masonry Blockwork External - wall tie requirements
Maximum Net Surface Wind Pressure
Cullen FT-100 = 1.279kN/m 2 3.7 ties/m 2 (450mm vertical & 600mm horizontal centres)
mber Gable to Masonry Blockwork External - wall tie requirements mber Gable to Masonry Blockwork External - wall tie requirements mber Gable to Masonry Blockwork External - wall tie requirements Cullen FT-100 = 2.558kN/m 2 7.4 ties/m 2 (225mm vertical & 600mm horizontal centres)
Minimum of 1 tie must be positioned in this zone at 600mm horizontal centres. 2 sets of wall ties with at least 1 tie positioned within 225mm of top of gable panel. Ties positioned at maximum of 225mm vertical & 600mm horizontal centres. Wall ties for general area positioned at maximum of 450mm vertical & 600mm horizontal centres (vertical centres can be reduced to 225mm if required by Building Designer). 2 sets of wall ties positioned at maximum of 225mm vertical & 600mm horizontal centres from bottom of gable panel. Top row of masonry wall ties provided at 300mm centres maximum.
Minimum of 1 tie must be positioned in this zone at 600mm horizontal centres.
600 600
600 600
600 600
600 600
600 600
600 600
600
600
600
600
600
600
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 7
Gable Restraint System
Timber Gable to Masonry Brickwork External - wall tie requirements
Maximum Net Surface Wind Pressure
Cullen FT-100 = 1.279kN/m 2 3.7 ties/m 2 (450mm vertical & 600mm horizontal centres)
mber Gable to Masonry Brickwork External - wall tie requirements Cullen FT-100 = 2.558kN/m 2 7.4 ties/m 2 (225mm vertical & 600mm horizontal centres) imber Gable to Masonry Blockwork External - wall tie requirements imber Gable to Masonry Blockwork External - wall tie requirements
Minimum of 1 tie must be positioned in this zone at 600mm horizontal centres. 2 sets of wall ties with at least 1 tie positioned within 225mm of top of gable panel. Ties positioned at maximum of 150mm vertical & 600mm horizontal centres. Wall ties for general area positioned at maximum of 450mm vertical & 600mm horizontal centres (vertical centres can be reduced to 225mm if required by Building Designer) 2 sets of wall ties positioned at maximum of 150mm vertical & 600mm horizontal centres from bottom of gable panel. Top row of masonry wall ties provided at 300mm centres maximum.
Minimum of 1 tie must be positioned in this zone at 600mm horizontal centres.
600
600 600 600
600 600 600
600 600 600
600 600 600
600
600 600
600 600
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 8
Jointing of panels
Jointing of panels
Fixing must be positioned maximum of 150mm from edge of panel (top & bottom)
38 x 89mm panels - PSTS-6.5 x 65mm screws at maximum of 333mm centres
47 x 97mm panels PSTS-8 x 85mm screws at maximum of 500mm centres
To meet the requirements of EN1995-1-1:2004+A2:2014 “the required vertical connection strength between two panels should be evaluated but should have a design strength of at least 2,5 kN/m”.
To achieve this panels are to be fixed using the following Paslode structural timber screws or the Paslode nail fixing.
Panel thickness where screw head is located (mm)
Panel thickness where screw point is located (mm)
Fixing type
Fixing Centres (mm)
PSTS-6.5 x 65 PSTS-8 x 85 Paslode 3.1 x 65 Paslode 3.1 x 90
38 47 38 47
38 47 38 47
333 500 130 130
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 9
Gable Restraint System
Class 2a Buildings / houses of single occupancy five storeys or less England & Wales and four storeys or less Scotland
Timber Gable to Masonry fixing detail to cold roofs – continuous wallplate
Gable Panel
225mm maximum height between underside of wallplate and horizontal restraint strap
Insulation continued into gable panel
Breather membrane to face of gable panel
Roof insulation Longitudinal truss bracing
Continuous wallplate 38mm min-75mm maximum depth Cullen FT Timber frame wall ties
Level of truss wallplate
Solid blocking between truss and gable panel at horizontal restraint strap positions Gable Panel to wallplate fixing - Paslode 3.1mm dia x min 75mm long smooth shank nails at maximum 100mm centres Vertical holding down strap plugged and screwed to blockwork at maximum 1.8m centres, Cullen VRS-900-100
Mortar bed
Cullen RST-3 restraint straps at maximum 750mm centres fixed to longitudinal truss bracing / additional longitudinal bracing with 8 no. 4 x 25mm steel screws fixed to gable panel stud with 3 no. 3.4 x 35mm square twist nails
Cullen Gable Restraint Bracket (GRB) at maximum 750mm centres Cavity insulation shown for indicative purposes only - thermal bridging and SAP calculations to be plot specific
Cavity trays and firestops to be detailed by building designer
Gable Panel (without gable ladder)
Cullen PFS restraint straps fixed to solid timber noggins between trusses at maximum 1250mm centres with 3.4 x 35mm square twist nails, 8 no. to noggins and 4 no. to gable panel (2 no. top face & 2 no. cavity face) Cullen RST-3 restraint straps at maximum 800mm centres fixed to additional longitudinal bracing with 8 no. 4 x 25mm steel screws fixed to gable panel stud with 3 no. 3.4 x 35mm square twist nails
Truss profile
Gable Panel (with or without gable ladder)
Continuous wallplate 38mm min-75mm maximum depth Bottom rail of gable panel
800mm max 800mm max
800mm max
800mm max800mm max
Mortar bed
750mm max 750mm max 750mm max 750mm max
Cullen Gable Restraint Bracket (GRB) at maximum 750mm centres
Cullen VRS-900-100 fixed to top of bottom rail with 4 no. 3.4 x 35mm square twist nails
1800mm maximum
Vertical restraint strap plugged and screwed to blockwork at maximum 1.8m centres - Cullen VRS-900-100 installed to top of gable panel bottom rail
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 10
Class 2a Buildings / houses of single occupancy five storeys or less England & Wales and four storeys or less Scotland Timber Gable to Masonry fixing detail to cold roofs – raised gable wallplate
Cavity trays and firestops to be detailed by building designer Gable Panel
Breather membrane to face of gable panel
Insulation continued into gable panel
Cullen FT Timber frame wall ties Mortar bed Wallplate 38mm min- 75mm maximum depth Levels to be adjusted to ensure top of bracing inline with top of blockwork Cullen Gable Restraint Bracket (GRB) at maximum 750mm centres Cavity insulation shown for indicative purposes only - thermal bridging and SAP calculations to be plot specific
Roof insulation
Longitudinal truss bracing (depth can vary to suit blockwork level)
Level of truss wallplate
Solid blocking between truss and gable panel at horizontal restraint strap positions Gable Panel to wallplate fixing - Paslode 3.1mm dia x min 75mm long smooth shank nails at maximum 100mm centres Vertical holding down strap plugged and screwed to blockwork at maximum 1.8m centres, Cullen VRS-900-100
Cullen PFS-1500-100-B restraint straps fixed to longitudinal truss bracing / additional longitudinal bracing at maximum 1.25m centres with 8 no. 4 x 25mm steel screws
Gable Panel (with or without gable ladder)
Cullen PFS restraint straps fixed to solid timber noggins between trusses at maximum 1250mm centres with 3.4 x 35mm square twist nails, 8 no. to noggins and 4 no. to gable panel (2 no. top face & 2 no. cavity face)
Gable Panel (without gable ladder)
Truss profile
Cullen PFS restraint straps bedded in mortar joint between top of masonry and wallplate and fixed to longitudinal truss bracing maximum 1250mm centres with 8 no. 4 x 25mm steel screws
Bottom rail of gable panel
Continuous wallplate 38mm min-75mm maximum depth
1250mm max
1250mm max
1250mm max
Mortar bed
750mm max 750mm max 750mm max 750mm max
Cullen Gable Restraint Bracket (GRB) at maximum 750mm centres
Cullen VRS-900-100 fixed to top of bottom rail with 4 no. 3.4 x 35mm square twist nails
1800mm maximum
Vertical restraint strap plugged and screwed to blockwork at maximum 1.8m centres - Cullen VRS-900-100 installed to top of gable panel bottom rail
Copyright © 2023 ITW All rights reserved. This document (including text, material, pictures, specifications and dimensions contained in it) may not be reproduced, transmitted or distributed or otherwise used in any way or by any means, except with the prior express permission of ITW Construction Products Offsite.
The latest version of the technical guide will always be the digital format on our website.
Technical support: 01592 771132 / technical@itwcp.com / https://www.itwcp-offsite.co.uk 11
Brands for the offsite industry
Cullen Technical Support email: technical@itwcp.com
May 2024*
*Subject to change at discretion of ITW Construction Products Offsite