Cullen Gable Restraint System

Timber Gable to Masonry Blockwork External - wall tie requirements Maximum Net Surface Wind Pressure

Cullen FT-100 = 1.279kN/m 2 3.7 ties/m 2 (450mm vertical & 600mm horizontal centres)

Cullen FT-100 = 2.558kN/m 2 7.4 ties/m 2 (225mm vertical & 600mm horizontal centres)

Minimum of 1 tie must be positioned in this zone at 600mm horizontal centres. 2 sets of wall ties with at least 1 tie positioned within 225mm of top of gable panel. Ties positioned at maximum of 225mm vertical & 600mm horizontal centres. Wall ties for general area positioned at maximum of 450mm vertical & 600mm horizontal centres (vertical centres can be reduced to 225mm if required by Building Designer).

Minimum of 1 tie must be positioned in this zone at 600mm horizontal centres.

2 sets of wall ties positioned at maximum of 225mm vertical & 600mm horizontal centres from bottom of gable panel.

Top row of masonry wall ties provided at 300mm centres maximum.