control enclosure are 2 port s also labeled “HIGH” and “LOW”. Interconnect the ports between the collector and pulse control with air tight tubing.
10.10 Nominal Full Load Amperes are as follows:
Voltage
Horse Power
208V
230V
460V
575V
3
10.0
8.0
4.0
3.5
5
15.00
13.0
6.5
5.0
7.5
20.0
18.0
9.0
7.0
10
30.0
24.0
12.0
10.0
15
40.0
37.0
18.5
15.0
20
55.0
48.0
24.0
20.0
25
70.0
60.0
30.0
24.0
30
78.0
71.0
35.5
28.0
40
110
92
46
37
50
130
110
55
45
11.0 SMOKE DETECTION/FIRE SUPPRESSION (OPTIONAL)
NOTE: All smoke detection/fire suppression installations must be performed by a qualified technician and in accordance with local, state, and national codes/regulations/laws (if any).
11.1 Smoke detection and fire suppression is an important aspect of the installation procedure. Fires are a common occurrence in dust collection systems and the comprehensive collection system should be designed for when a fire occurs, not if. Various systems are available for smoke detection and an even greater list of fire suppression technologies exist. Fire sprinkler systems for collectors MUST be properly connected. In most cases, this is the closest building’s fire sprinkler system. ALL smoke detection/fire suppression systems should be periodically inspected and maintained.
12.0 PRE-START UP
12.1 If not already verified in the electrical section, check rotation of fan by tur ning “ON” for a brief instant (JOG) and verifying rotation. Rotation must be clockwise when viewed “OVER THE MOTOR” from the discharge side. If the rotation is correct, start the motor.
12.2 Check that rotary air locks, screw conveyors or any other directional dependent components are rotating the correct direction.
12.3 Check the compressed air system for leaks. Confirm 90 PSI minimum air pressure and 100 PSI maximum air pressure.
12.4 Ensure that no air leaks exist in the seams of any field assembled cabinet components such as hoppers, dust drawers, plenums, filter cabinets, drum lid kits, drums, etc. Warning: Compressed air pressure higher than 100 PSI can damage the filters and the dust collector’s structural integrity.
Page 12