1 AD1.15
2 AD1.15
TO 12TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
2" SYSTEM CONTROL VALVE AND RISER MANIFOLD FOR 1st FLOOR SYSTEM
TO 11TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
4" RISER TO BULK MAIN AND FDC
6" GROOVED BUTTERFLY VALVE W/ TAMPER SWITCH
TO 10TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
2" MAIN DRAIN WATER PRESSURE GAUGE
6" FLANGED OS&Y GATE VALVE W/ TAMPER SWITCH
North Elevation
6" AMES 3000SS DCDA W/ TAMPER SWITCHES
1" = 10'-0" 2
TO 9TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
1" OUTLET FOR JOCKEY PUMP DISCHARGE
6" GROOVED BUTTERFLY VALVE W/ TAMPER SWITCH
TO 8TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
TO WATER SERVICE
4" x 1'-10" PUMP SPOOL
6" GROOVED CHECK VALVE
TO 7TH FLOOR SYSTEM
6 x 4 GROOVED ECCENTRIC REDUCER
6 x 4 GROOVED CONCENTRIC REDUCER
TO TEST HEADER
2 1
2 " HOSE VALVE
VERTICAL IN-LINE ELECTRIC FIRE PUMP 750 GPM @ 100 PSI
TO 6TH FLOOR SYSTEM
FIRE PUMP ASSEMBLY SCALE: N.T.S.
2 1
2 " HOSE VALVE
TO 5TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
TO 4TH FLOOR SYSTEM
2 1
2 " HOSE VALVE
TO 3RD FLOOR SYSTEM
1 AD1.16
2 1
2 " HOSE VALVE
TO 2ND FLOOR SYSTEM
[ô[ô)/86+02817(')'& w/ 10" EXTERIOR ALARM BELL ABOVE [ô[ô[ô)/86+02817(' FIRE PUMP TEST HEADER
RISER MANIFOLD WITH TAMPERED CONTROL VALVE
2 1
2 " HOSE VALVE
TO LOBBY LEVEL SYSTEM
2 1
2 " HOSE VALVE
FIRE PUMP (SEE DETAIL)
STANDPIPE SCHEMATIC SCALE: 3/16 " = 1'-0"
FIRE PROTECTION RISER DIAGRAM Stonegate 2401 West Higgins Road Hoffman Estates, IL
Return to Table of Contents
Made with FlippingBook flipbook maker