LCI Preconstruction & Estimating Training Manual

11/22/2017

Sprinkler Head Types

Density

Design

Side Wall

Upright

Pendant

ESFR

Hazard

Semi Recessed

Concealed

What Are You Protecting?

Upright Sprinkler Heads

Density

Hazard

• Determine need of water for building • Depends on following: ▫ Building usage ▫ Hazard ▫ Area limitation of heads

• Determines density • Multiple hazards within a facility ▫ Light Hazard

• Standard Response Sprinkler Head • Sit upright on piping system • Typical response temperature ▫ 165 ° F • Usually used in City of Chicago • Typically $10 each

▫ Ordinary I ▫ Ordinary II ▫ Extra Hazard

Density Hazard Purpose(Type of Facility)

Total Coverage (SF)

Sprinkler Head Coverage (SF)

Pendant Sprinkler Head (1)

-Offices -Hospital -Educational

Light Hazard

0.10

52,000

225

-Restaurant -Retail -Parking Garages -Repair garages -Libraries

• Concealed Sprinkler Head • Usually in office buildings • Typical response temperature: ▫ 130°F • Concealment pops off once response temperature is reached • Typically $12 each

Ordinary I

0.15

52,000

130

Ordinary II

0.20

52,000

130

-Die Casting -Printing - Combustible Liquid

Extra Hazard

0.25

40,000

100

20

Return to Table of Contents