Leopardo Proposed Technical Center Outline Specifications Page 25 of 25 12/13/2012
16.7. Lighting
a) Office and Technical Lighting i. Provide lighting type and locations as identified in Technical Criteria Matrix. ii. Where indicated, parabolic fixtures shall be 4” deep, recessed parabolic lay-in type, 2’-0” x 4’-0” fluorescent fixtures similar or equal to Lithonia’s three lamp fluorescent fixture providing 40 FC @ 36" above floor with dual level switching. iii. Fluorescent lighting to be E-Ballast, full color spectrum, Type T-8 (office areas),
Type T5 High Output (shop areas) or High Frequency fluorescent bulbs (dynamometer test cells) as indicated in the Technical Criteria Matrix
iv. Where indicated in the Technical Criteria Matrix, T-5 High Output lamps shall be in a 4-lamp F-Bay fluorescent fixture providing 60 FC @ 36" above floor. v. Dynamometer Test Cell lighting shall be High Frequency Fluorescent Lighting mounted in explosion resistant fixtures and located so as to minimize shadows and provide 650 lux (60FC) @ 36" above floor. vi. Fixtures that are neither parabolic nor F-Bay type may use A12 prismatic lenses. vii. Provide dimmable compact fluorescent down lights in conference rooms, lobby and for Vice President / Director offices. viii. All lighting to be operated by switches or dimmable controls. ix. Provide night lighting controlled by locked-on circuits in lighting panels, exit lighting and emergency lighting as required by code. x. Rooms with more than one door shall have three or four-way light switches as appropriate at each door. xi. Provide rechargeable battery packs for fluorescent fixtures emergency exit lights. b) Site Lighting i. Provide electrical for exterior and building signage as required. ii. Provide lighting for three (3) flagpoles. iii. Provide exterior lighting control with seven-day time clock control. iv. Provide 100 watt, high-pressure sodium, bracket mounted, weatherproof light fixtures at each exterior personnel access door and overhead doors and truck wells. v. Provide aluminum or steel light poles on concrete bases with luminaries in parking and roadway areas for primary site lighting as required and allowed by local code. vi. Provide exterior 400-watt wall pack fixtures for supplemental site lighting. vii. Provide $15,000 allowance for monument sign and lighting.
<end>
Return to Table of Contents
Made with FlippingBook flipbook maker