RTT Booth & AMU Detailed Start-Up Guide

12

d1f. Check burner profile pressure, and manually close profile as needed to achieve .5” to .7”. Tighten the mechanical stop on the actuator at the new location so that the damper cannot fully open during spray mode.

Release Clutch Button (Press & Hold to manually turn actuator/damper by hand)

Profile Damper Actuator

Cure Mode Stop Position

Damper Position Indicator

Spray Mode Stop Position

Turn the damper shaft towards the closed position until you achieve the desired .6” w.c. on the manometer, then adjust the “Spray Mode Stop Position” screw so that it butts up against the actuators new position.

Manometer reading .6” w.c. air pressure across the burner profile opening.

d1g. Check booth pressure to see if it is at least -0.099 d1h. Repeat steps d1e through d1g until profile pressure is .5” to .7” and booth pressure is -0.099. If the AMU VFD must be set lower than 48hz, then there may be some other problem with the exhaust system. Check the exhaust duct, filters, fan serial plate, motor HP, belt tension, etc. to ensure all other external factors are accounted for. d1i. Ensure P42 is set lower than P1