8
Upon Arrival At Job Site
b1. _____ Ensure filters are correctly installed at the intake of the AMU (don’t skip this step – system cannot be properly setup and balanced if filters are not correctly installed.) b2. _____ Ensure filters are correctly installed and new at the intake of the booth (don’t skip this step – system cannot be properly setup and balanced if filters are not correctly installed.). The green/blue side of the filter is sticky and should be on the down stream side of the air flow (sticky side of filter in the work area). b3. _____ Ensure filters are correctly installed and new at the exhaust of the booth (don’t skip this step – system cannot be properly setup and balanced if filters are not correctly installed.) b4. _____ Ensure the plumber has purged the fuel line of air. b5. _____ Ensure exhaust motor(s) are wired for proper voltage (don’t skip this step – its very common for the motors to be wired incorrectly which will cause issues later on in this guide.)
b5a. L1 wire from the control panel is connected to: _________________ on the motor
b5b. L2 wire from the control panel is connected to: _________________ on the motor
b5c. L3 wire from the control panel is connected to: _________________ on the motor
b5d. ____________________ on the motor are tied together
b5e. ____________________ on the motor are tied together
b5f. ____________________ on the motor are tied together b6. _____ Write down (or take photo) the details on the exhaust motor(s) name plate
b6a. CAT Number: ____________________
b6b. HP: ____________________________
b6c. FLA: ____________________________ b7. _____ Ensure any fire suppression in or around the booth is rated for temperature capabilities of the AMU. (If sprinkler heads are Orange, Red, or Yellow they may be too low – check with fire suppression specialist if unsure. High temperature limit is set at 250F, so the heads need to be higher than that) b8. _____ Ensure the pressure tube from the booth wall to the remote control panel is connected to the + side of the pressure sensor. The minus side of the sensor should be ran to outside of the control panel. b9. _____ Ensure the “telephone plug” in the remote panel is not plugged in. Voltage needs to be confirmed before plugging in the cable. b10. _____ Ensure the AMU motor has been wired to control panel, and that the belts/pulley/drive are secure. b11. _____ Write down (or take photo) the details on the AMU motor name plate
b11a. Model number: __________________
b11b. HP: ____________________________
b11c. FLA: ___________________________
8
Made with FlippingBook - professional solution for displaying marketing and sales documents online