Bid Proposal 1093-2 Security Camera Replacement Graphics

3

1

2

4

D

COMMUNITY COLLEGE OF ALLEGHENY COUNTY SECURITY CAMERA REPLACEMENT PROJECT

C

SITE LOCATION

B

A

HFL 2021-2019

3

4

1

2

3

1

2

4

O C S B U I L D I N G

D

EXISTING 1-1/2" POWER AND 1-1/2" SIGNAL CONDUITS

N . L I N C O L N A V E .

EXISTING (2) 4" CONDUITS

KEYNOTES: 1. REMOVE EXISTING CAMERA AND CABLE TO BUILDING THEN TO SOURCE - KEEP CONDUIT (ATTACHED TO GUIDE RAIL). CONDUIT ON GUIDE RAIL BECOMES SPARE. 2. REPLACE EXISTING CAMERA WITH NEW INTERCOM CAMERA 3. REMOVE EXISTING INTERCOM - TAG WIRE AS SPARE - PROVIDE COVERPLATE. 4. REFERENCE DETAILS 1,2,3 ON SHEET E504.

EMERGENCY PHONE ETR

ETR

ETR

ETR

ETR

J

1

1

EXISTING HANDHOLE HH#1

EXISTING EXIT GATE

C

EXISTING (2) 4" CONDUITS

ETR

EXISTING PULL BOX WITH GATE PANEL

ETR

ETR

ETR

ETR

EXISTING (3) 1" CONDUITS

ETR

2

IC EXT

EXISTING ENTRANCE GATE

3

1

1

1

ETR

270°

ETR

ETR

ETR

4

ETR EXT FOUR EXISTING

CAMERAS TO REMAIN

B

EXISTING LIGHT POLE TYPICAL

EXISTING POWER HANDHOLE

EXISTING HANDHOLE HH#2

CCAC PARKING LOT SITE PLAN - SECURITY

1

0

10'

20'

40'

Scale: 1" = 20'-0"

A

CALL BEFORE YOU DIG! PENNSYLVANIA LAW REQUIRES 3 WORKING DAYS NOTICE FOR

SCALE: 1" = 20'-0"

CONSTRUCTION PHASE AND 10 WORKING DAYS IN DESIGN STAGE - STOP CALL

POCS SERIAL NUMBER

SYSTEM, INC.

HFL 2021-2019

3

4

1

2

3

1

2

4

SYMBOL & ABBREVIATION SCHEDULE

NOTES:

POWER LEGEND

GENERAL NOTES - ELECTRICAL

MISCELLANEOUS ELECTRICAL LEGEND

ABBREVIATIONS

D

ELECTRICAL PANEL BOARD - SURFACE MOUNTED

A

AQUASTAT - SUPPLIED BY OTHERS, WIRED BY EC

ELECTRICAL PANEL BOARD - RECESSED

BB

BACK BOX

MULTI-OUTLET ASSEMBLY (RATING AS NOTED)

CB

POWER ENCLOSED CIRCUIT BREAKER

1

INDICATES NOTES ELSEWHERE

EMERGENCY POWER OFF

EPO

Ø

PHASE

H

HUMIDISTAT - SUPPLIED BY OTHERS, WIRED BY EC

BUSWAY

R

RELAY

SWITCH LEG

T

TRANSFORMER

BRANCH CIRCUIT

WS

PWR - WATOR SENSOR

SWITCHED CIRCUIT

FINAL CONNECTION BY EC TO EQUIPMENT

HOMERUN TO PANEL BOARD - 3 #12-3/4"C UNO

COMBINATION DISCONNECT SWITCH AND STARTER

CROSS HATCHING INDICATES EQUIPMENT AND/OR WIRING TO BE RENDERED DEAD AND REMOVED BY EC.

FUSED DISCONNECT SWITCH

C

NON-FUSED DISCONNECT SWITCH

MAGNETIC MOTOR STARTER

ELECTRIC THERMOSTAT BY OTHERS UNLESS NOTED OTHERWISE AND WIRED BY EC

RECEPTACLES LEGEND

M

MOTOR

AB

VOLTAGE DROP NOTE:

B

· · ·

A

HFL 2021-2019

3

4

1

2

3

1

2

4

1. ALL EXPOSED CABLE SHALL BE RUN IN CONDUIT, ON EXISTING CABLE TRAY OR SECURED TO CABLE TRAY UTILIZING J-HOOKS UNO. FIELD COORDINATE ALL CONDUIT ROUTES. PROVIDE ALL SUPPORT MATERIALS AND HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE JUNCTION 2. FIELD COORDINATE ALL FINAL CONDUIT SLEEVE AND PENETRATION LOCATIONS TO AVOID ANY EXISTING OBSTRUCTIONS. SEAL ALL THRU WALL/FLOOR PENETRATIONS AS REQUIRED PER IBC. 3. USE OF CABLE ZIP TIES TO PREVENT OVER TIGHTENING AND DAMAGE TO CABLES IS PROHIBITED. 4. ALL CABLES ARE TO BE ROUTED TO RACK G08 ON THE THIRD FLOOR IN THE DATA CENTER. 5. DO NOT MODIFY STRUCTURAL MEMBERS LOCATED IN CHASEWAY. BOXES AS REQUIRED. GENERAL NOTES (APPLIES TO ALL DRAWINGS):

3

D

EXT-9

1

J

J

9

1

9

KEYNOTES:

1. PROVIDE 6"x6"x4" JUNCTION BOX. FIELD COORDINATE EXACT LOCATION. 2. PROVIDE BUSHINGS ON CONDUIT ENDS - ROUTE CABLE VIA SLEEVES TO THIRD FLOOR. PROVIDE 2" SLEEVE TO FIRST FLOOR AND (2) SPARE 2" SLEEVES. ROUTE CABLE THROUGH BASEMENT. 3. FIELD COORDINATE EXTERIOR CAMERA MOUNTING HEIGHT. ESTIMATED HEIGHT 12'-0". 4. REMOVE EXISTING CAMERA AND CABLE BACK TO SOURCE. 5. CONDUITS TO PARKING CONTROLS AND PANEL BOARD. INTERCEPT COAX CABLE ROUTED TO PARKING GATE PEDISTAL MOUNTED CAMERA. PROVIDE COAX TO CAT6 IMPEDANCE MATCHING DEVICE. ROUTE CAT6 TO DATA CENTER ON 3RD FLOOR. REMOVE INTERIOR COAX CABLE. 6. NOT USED. 7. PROVIDE 2" SLEEVE FOR PENETRATION THROUGH WALL. 8. FIELD COORDINATE EXTERIOR CAMERA MOUNTING HEIGHT. ESTIMATED HEIGHT 12'-0". ROUTE CABLE THROUGH BASEMENT. 9. CAT6 CABLE TO BE ROUTED THROUGH BASEMENT TO EACH CAMERA LOCATION. SECURE CABLE TO CEILING EVERY FIVE FEET.

8

270°

EXT-5

J

1

9

J

1

C

9

PROVIDE AND INSTALL 2" SLEEVE TO FIRST FLOOR

1

9

1

J

J

012B-1

EXT-6

4

9

180°

2

012A-1

J

9

1

7

EXISTING PANEL PBX 120/208V, 60A, MLO

J J

J

B

5

1

015-1

EXISTING (2) 4" EMT TO PARKING LOT, ETR

ALTERNATE 1

BASEMENT FLOOR - SECURITY

1

Scale: 1/8" = 1'-0"

0

8'

16'

4'

SCALE: 1/8" = 1'-0"

A

HFL 2021-2019

3

4

1

2

3

1

2

4

11 7 8

GENERAL NOTES (APPLIES TO ALL DRAWINGS): 1. ALL EXPOSED CABLE SHALL BE RUN IN CONDUIT, ON EXISTING CABLE TRAY OR SECURED TO CABLE TRAY UTILIZING J-HOOKS UNO. FIELD COORDINATE ALL CONDUIT ROUTES. PROVIDE ALL SUPPORT MATERIALS AND HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE JUNCTION BOXES AS REQUIRED. 2. FIELD COORDINATE ALL FINAL CONDUIT SLEEVE AND PENETRATION LOCATIONS TO AVOID ANY EXISTING OBSTRUCTIONS. SEAL ALL THRU WALL/FLOOR PENETRATIONS AS REQUIRED PER IBC. 3. USE OF CABLE ZIP TIES TO PREVENT OVER TIGHTENING AND DAMAGE TO CABLES IS PROHIBITED. 4. ALL CABLES ARE TO BE ROUTED TO RACK G08 ON THE THIRD FLOOR IN

6

270°

EXT-3

PLANTER

D

3/4" CONDUIT

6

9

J

ROUTE CABLE ON J-HOOKS ABOVE ACT

THE DATA CENTER.

7

5. DO NOT MODIFY STRUCTURAL MEMBERS LOCATED IN CHASEWAY.

125-1 180°

KEYNOTES: 1. REMOVE EXISTING "66 WIRING BLOCKS" AND TELEPHONE COPPER WIRING IN EXISTING RISER. KEEP EXISTING PLYWOOD. 2. PROVIDE AND INSTALL 2" SLEEVE FOR PENETRATION TROUGH WALL 3. PROVIDE AND INSTALL 2" HORIZONTAL SLEEVE FOR ACCESS TO RISER. REMOVE RECESSED LIGHTING FIXTURE AT EXISTING BULKHEAD RISER LOCATION. PROVIDE (2) LED FIXTURES AT NEW BULKHEAD - DAYBRITE 1-SDL-27L-835-4-D-UNV-GLR - RECIRCUIT TO NEW FIXTURES. 4. PROVIDE AND INSTALL (2) 2" SLEEVES AT EACH FLOOR FOR FUTURE ABOVE CEILING. 5. WORK. FIELD COORDINATE EXTERIOR CAMERA MOUNTING HEIGHT. ESTIMATED HEIGHT 15'-0". ROUTE CABLE TO FIRST FLOOR CEILING. 6. REMOVE EXISTING CAMERA AND CABLE BACK TO SOURCE. 7. EXTEND 3/4" CONDUIT TO ABOVE CEILING IN CORRIDOR. 8. CONCEAL CABLE ABOVE CEILING VIA J-HOOKS AND CABLE TRAY TO RISER. 9. PROVIDE AND INSTALL 6"x6"x4" JUNCTION BOX. FIELD COORDINATE EXACT LOCATION. 10. FIELD COORDINATE EXTERIOR CAMERA MOUNTING HEIGHT. ESTIMATED HEIGHT 12'-0". ROUTE CABLE TO FIRST FLOOR CEILING. 11. FIELD COORDINATE EXTERIOR CAMERA MOUNTING HEIGHT. ESTIMATED HEIGHT 12'-6". ROUTE CABLE TO FIRST FLOOR CEILING.

3/4" CONDUIT

9

PEDESTAL

ETR

J

ETR

IC

CAM

6

8

EXT-4

6

IC CAM

EXT-2

100K-1

8

6

8

C

PROVIDE AND INSTALL WIREMOLD 500 FROM CAMERA TO ABOVE CORRIDOR WITH 1" WALL SLEEVE.

2

100F-1 180°

8

100B-1

101-1

8

1 3 4

8

360°

2

6

2

6

101-2

PROVIDE AND INSTALL 2" SLEEVE TO BASEMENT

B

PROVIDE AND INSTALL 2" SLEEVE TO 2ND FLOOR

8

EXT-1

IC CAM

270°

270°

8

5

10 8

6

EXT-7

EXT-8

FIRST FLOOR - SECURITY

1

0

8'

16'

4'

Scale: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

A

HFL 2021-2019

3

4

1

2

3

1

2

4

GENERAL NOTES (APPLIES TO ALL DRAWINGS): 1. ALL EXPOSED CABLE SHALL BE RUN IN CONDUIT, ON EXISTING CABLE TRAY COORDINATE ALL CONDUIT ROUTES. PROVIDE ALL SUPPORT MATERIALS AND HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE JUNCTION BOXES AS REQUIRED. 2. FIELD COORDINATE ALL FINAL CONDUIT SLEEVE AND PENETRATION LOCATIONS TO AVOID ANY EXISTING OBSTRUCTIONS. SEAL ALL THRU WALL/FLOOR PENETRATIONS AS REQUIRED PER IBC. 3. USE OF CABLE ZIP TIES TO PREVENT OVER TIGHTENING AND DAMAGE TO CABLES IS PROHIBITED. 4. ALL CABLES ARE TO BE ROUTED TO RACK G08 ON THE THIRD FLOOR IN THE DATA CENTER. 5. DO NOT MODIFY STRUCTURAL MEMBERS LOCATED IN CHASEWAY. KEYNOTES: 1. REMOVE EXISTING "66 WIRING BLOCKS" AND TELEPHONE COPPER WIRING IN EXISTING RISER. KEEP EXISTING PLYWOOD AND DUPLEX RECEPTACLE. 2. CONCEAL CABLE ABOVE CEILING VIA J-HOOKS AND CABLE TRAY TO RISER. 3. PROVIDE AND INSTALL 2" HORIZONTAL SLEEVE FOR ACCESS TO RISER. REMOVE RECESSED LIGHTING FIXTURE AT EXISTING BULKHEAD RISER LOCATION. PROVIDE AND INSTALL (2) LED FIXTURES AT NEW BULKHEAD - DAYBRITE 1-SDL-27L-835-4-D-UNV-GLR - RECIRCUIT TO NEW FIXTURES. 4. PROVIDE AND INSTALL (2) 2" SLEEVES TO EACH FLOOR FOR FUTURE WORK.

D

C

200G-1

2

1 3 4

2

200E-1

PROVIDE AND

PROVIDE AND

ALTERNATE 1

INSTALL 2" SLEEVE TO 3RD FLOOR

INSTALL 2" SLEEVE TO 1ST FLOOR

ALTERNATE 1

B

SECOND FLOOR - SECURITY

1

0

8'

16'

4'

Scale: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

A

HFL 2021-2019

3

4

1

2

3

1

2

4

1

2

3

4

5

6

7

8

5A

6A

GEN DRA

7A

1. ALL EXPOSED CABLE SHALL BE RUN IN CONDUIT, ON EXISTING CABLE TRAY COORDINATE ALL CONDUIT ROUTES. PROVIDE ALL SUPPORT MATERIALS AND HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE JUNCTION BOXES AS REQUIRED. 2. FIELD COORDINATE ALL FINAL CONDUIT SLEEVE AND PENETRATION LOCATIONS TO AVOID ANY EXISTING OBSTRUCTIONS. SEAL ALL THRU WALL/FLOOR PENETRATIONS AS REQUIRED PER IBC. 3. USE OF CABLE ZIP TIES TO PREVENT OVER TIGHTENING AND DAMAGE TO CABLES IS PROHIBITED. 4. ALL CABLES ARE TO BE ROUTED TO RACK G08 ON THE THIRD FLOOR IN THE DATA CENTER. 5. DO NOT MODIFY STRUCTURAL MEMBERS LOCATED IN CHASEWAY. KEYNOTES: 1. REMOVE EXISTING "66 WIRING BLOCKS" AND TELEPHONE COPPER WIRING IN EXISTING RISER. KEEP EXISTING PLYWOOD AND 4-PLEX RECEPTACLE. 2. PROVIDE AND INSTALL 4" SLEEVE FOR PENETRATION TROUGH WALL ABOVE CEILING. 3. PROVIDE AND INSTALL 2" HORIZONTAL SLEEVE FOR ACCESS TO RISER. REMOVE RECESSED LIGHTING FIXTURE AT EXISTING BULKHEAD RISER LOCATION. PROVIDE AND INSTALL (2) LED FIXTURES AT NEW BULKHEAD - DAYBRITE 1-SDL-27L-835-4-D-UNV-GLR - RECIRCUIT TO NEW FIXTURES. 4. PROVIDE AND INSTALL (2) 2" SLEEVES TO EACH FLOOR FOR FUTURE WORK. 5. PROVIDE AND INSTALL WIREMOLD 500 TO ABOVE CORRIDOR CEILING WITH 1" SLEEVE AT WALL. 6. REMOVE CAMERA AND CABLE TO SOURCE.

Z

D

321

322

Y

323

320

300i

X

319

324

A

325

C

326

316

317

318

327

300J

316-1 360°

G8

B

304C

G7

300D

360° 316-5

300K

G6

300B

328

G5

304B PROVIDE AND INSTALL 2" SLEEVE TO 4TH FLOOR

5

G4

329

304A

316-3 360°

300F

G3

300C

G2

2

G1

315

1

330

360°

3

4

300A

304

306

300

316-4

300G

C

300E

300E-1

300-1

B

PROVIDE AND INSTALL 2" SLEEVE TO 2ND FLOOR

331

314

312

311

310

309

308

307

305

303

302

301

313

D

THIRD FLOOR - SECURITY 0

1

8'

16'

4'

Scale: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

A

HFL 2021-2019

3

4

1

2

3

1

2

4

GENERAL NOTES (APPLIES TO ALL DRAWINGS): 1. ALL EXPOSED CABLE SHALL BE RUN IN CONDUIT, ON EXISTING CABLE TRAY COORDINATE ALL CONDUIT ROUTES. PROVIDE ALL SUPPORT MATERIALS AND HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE JUNCTION BOXES AS REQUIRED. 2. FIELD COORDINATE ALL FINAL CONDUIT SLEEVE AND PENETRATION LOCATIONS TO AVOID ANY EXISTING OBSTRUCTIONS. SEAL ALL THRU WALL/FLOOR PENETRATIONS AS REQUIRED PER IBC. 3. USE OF CABLE ZIP TIES TO PREVENT OVER TIGHTENING AND DAMAGE TO CABLES IS PROHIBITED. 4. ALL CABLES ARE TO BE ROUTED TO RACK G08 ON THE THIRD FLOOR IN THE DATA CENTER. 5. DO NOT MODIFY STRUCTURAL MEMBERS LOCATED IN CHASEWAY. KEYNOTES: 1. REMOVE EXISTING "66 WIRING BLOCKS" AND TELEPHONE COPPER WIRING IN EXISTING RISER. RELOCATE EXISTING PLYWOOD TO BACK OF RISER ACCESS PANEL 2. CONCEAL CABLE ABOVE CEILING VIA CABLE TRAY AND J-HOOKS. 3. PROVIDE AND INSTALL 2" HORIZONTAL SLEEVE FOR ACCESS TO RISER. REMOVE RECESSED LIGHTING FIXTURE AT EXISTING BULKHEAD RISER LOCATION. PROVIDE AND INSTALL (2) LED FIXTURES AT NEW BULKHEAD - DAYBRITE 1-SDL-27L-835-4-D-UNV-GLR - RECIRCUIT TO NEW FIXTURES. 4. PROVIDE AND INSTALL (2) 2" SLEEVES TO EACH FLOOR FOR FUTURE WORK.

D

C

400G-1

2

1 3 4

2

400E-1

PROVIDE AND INSTALL 2" SLEEVE TO 3RD FLOOR PROVIDE AND INSTALL 2" SLEEVE TO 5TH FLOOR

ALTERNATE 1

ALTERNATE 1

B

FOURTH FLOOR - SECURITY

1

0

8'

16'

4'

Scale: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

A

HFL 2021-2019

3

4

1

2

3

1

2

4

GENERAL NOTES (APPLIES TO ALL DRAWINGS): 1. ALL EXPOSED CABLE SHALL BE RUN IN CONDUIT, ON EXISTING CABLE TRAY COORDINATE ALL CONDUIT ROUTES. PROVIDE ALL SUPPORT MATERIALS AND HARDWARE FOR A COMPLETE INSTALLATION. PROVIDE JUNCTION BOXES AS REQUIRED. 2. FIELD COORDINATE ALL FINAL CONDUIT SLEEVE AND PENETRATION LOCATIONS TO AVOID ANY EXISTING OBSTRUCTIONS. SEAL ALL THRU WALL/FLOOR PENETRATIONS AS REQUIRED PER IBC. 3. USE OF CABLE ZIP TIES TO PREVENT OVER TIGHTENING AND DAMAGE TO CABLES IS PROHIBITED. 4. ALL CABLES ARE TO BE ROUTED TO RACK G08 ON THE THIRD FLOOR IN THE DATA CENTER. 5. DO NOT MODIFY STRUCTURAL MEMBERS LOCATED IN CHASEWAY. KEYNOTES: 1. REMOVE EXISTING "66 WIRING BLOCKS" AND TELEPHONE COPPER WIRING IN EXISTING RISER. RELOCATE EXISTING PLYWOOD TO BACK OF RISER ACCESS PANEL. 2. PROVIDE AND INSTALL 2" HORIZONTAL SLEEVE FOR ACCESS TO RISER. REMOVE RECESSED LIGHTING FIXTURE AT EXISTING BULKHEAD RISER LOCATION. PROVIDE AND INSTALL (2) LED FIXTURES AT NEW BULKHEAD - DAYBRITE 1-SDL-27L-835-4-D-UNV-GLR - RECIRCUIT TO NEW FIXTURES. 3. PROVIDE AND INSTALL (2) 2" SLEEVES TO EACH FLOOR FOR FUTURE WORK. 4. CONCEAL CABLE ABOVE CEILING VIA CABLE TRAY AND J-HOOKS.

D

508

515

511

513B

509

512

514

513

513A

513C

507

4

360°

360°

500G-2

500I

500G

4

500G-1

516

504C

C

516

500D

500J

504B

500C

500F

504A

503

500H

506

501A

505

500A

500E

180°

500J-1

516-1 270°

J

4

1

3

2

PROVIDE AND

ALTERNATE 1

WEATHER PROOF CAMERA AND BOX W/ GASKET

INSTALL 2" SLEEVE TO 4TH FLOOR

ALTERNATE 1

ROOF DECK

B

FIFTH FLOOR - SECURITY

1

0

8'

16'

4'

Scale: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

A

HFL 2021-2019

3

4

1

2

3

1

2

4

500 SERIES

D

GENERAL NOTES TO SECURITY CAMERA RISER - OCS BUILDING 1. RISER IS DIAGRAMMATIC AND REPRESENTS SECURITY CAMERA INSTALLATION THROUGHOUT THE FACILITY - PROVIDE ALL MOUNTING HARDWARE; ACTIVE COMPONENTS AND RACEWAYS AS REQUIRED FOR A COMPLETE AND OPERATING SYSTEM. 2. ALL CAMERAS SHALL BE SOURCED VIA CAT 6 CABLE ROUTED TO THE THIRD FLOOR DATA CENTER- FIELD COORDINATE ALL ROUTING. 3. NO CAMERA CABLE MAY BE EXPOSED - ROUTE CABLE IN RACEWAY OR ABOVE CEILINGS ON J-HOOKS - USE EXISTING CABLE TRAYS WHERE AVAILABLE. 4. PROVIDE CONDUIT SLEEVES WITH NYLON BUSHINGS AT ALL WALL PENETRATIONS. PROVIDE WIREMOLD JUNCTION BOXES AND ACCESSORIES WHERE WIREMOLD (SMR) IS CALLED FOR. SMR INSTALLATION SHALL TERMINATE IN SMR ACCESSORY BOXES. 5. FIRESTOP ALL PENETRATIONS INCLUDING CONDUIT SLEEVES. 6. SEE PLAN SHEETS FOR CAMERA AND INTERCOM CAMERA LOCATIONS. 7. SEE NOTES TO PARKING AREA CABLING FOR ADDITIONAL INFORMATION. 8. ALL CAT 6 AND FIBER CABLES SHALL BE TESTED CERTIFIED BY CONTRACTOR - PROVIDE 25 YEAR WARRANTY ON CABLES.

KEYED NOTES: 1. PROVIDE INTERFACE TO EXISTING LENEL DOOR ACCESS SYSTEM AND GATE CONTROL SYSTEM. PROVIDE ANY REQUIRED RELAYS; WIRING OR ACCESSORIES TO UNLOCK MAIN AND SIDE DOORS AND OPEN PARKING GATE FROM RECEPTION AREA. LOCKS AND MOTORS ARE EXISTING TO REMAIN. INTERCOMS ARE BEING REPLACED UNDER THIS CONTRACT. 2. FED VIA EXISTING FIBER FROM BYERS HALL.

ALTERNATE 1

5TH FLOOR

400 SERIES

ALTERNATE 1

CONDUIT SLEEVES TYPICAL

4TH FLOOR

300 SERIES

C

3RD FLOOR

EXISTING RACK G8

IN 3RD FLOOR DATA CENTER

200 SERIES

ALTERNATE 1

NOTES: 1.

SEE BASEMENT DRAWING FOR REFERENCE, E101.

POLE MOUNTED CAMERA - SEE DRAWING ES101

2ND FLOOR

EXT

EXT

EXT

EXT

EXT

EXT

100 SERIES

IC CAMERA TO EXISTING PEDISTAL - SOURCE TO EXISTING COAX

EXT

AND GATE CONTROL INTERFACE RECEPTION AREA - DOOR

1

EXISTING 4" EMT CONDUITS

1ST FLOOR

PUBLIC STREET

PARKING LOT

1ST FLOOR

B

HH#1

J

ALTERNATE 1

ETR

000 SERIES

EXT

EXT

EXT

EXISTING TELEPHONE RACK RM. 001A

CAT6 TO DATA

CENTER

INTERFACE DEVICE -COAX TO CAT6

TELEPHONE

BASEMENT

BASEMENT

UNDERGROUND - TO PARKING AREA

ROOM

SECURITY CAMERA RISER

1

Scale: NOT TO SCALE

A

HFL 2021-2019

3

4

1

2

3

1

2

4

CONDUIT BODY

EXTERIOR WALL

4" SQ. JUNCTION BOX W/ BLANK COVERS

MOUNTING BRACKET

FLEXIBLE CONUIT

D

EMT COMPRESSION FITTING EMT CONDUIT EMT STRAP

STRUCTURE

BACKBOX MOUNTING BRACKET

BACK OF CAMERA TO CEILING - FLEX CAN HIT FROM SIDE FASTENERS PER CAMERA INSTRUCTIONS

NOTE: COORDINATE W/ EQUIP MANUFACTURER FOR HARDWARE AND ACCESSORIES

NOTE: COORDINATE W/ EQUIP MANUFACTURER FOR HARDWARE AND ACCESSORIES

CORNER MOUNT CAMERA - EXTERIOR

EXPOSED CEILING MOUNTED CAMERA DETAIL

3

2

EXTERIOR CAMERA - LIGHT POLE MOUNTED DETAIL 1

Scale: NOT TO SCALE

Scale: NOT TO SCALE

Scale: NOT TO SCALE

C

STRUCTURAL CEILING

STRUCTURAL CEILING

ALL-THREAD SUPPORT

CONDUIT TO CABLE MANAGEMENT SYSTEM

CONDUIT CONNECTOR W/BUSHING

BEAM CLAMP

CAT 6 CABLE TO TELECOM ROOM

2-GANG WORKBOX W/SINGLE GANG PLATE

CONDUIT CONNECTOR W/BUSHING

2-GANG WORKBOX W/SINGLE GANG PLATE

CONDUIT TO ACCESSIBLE CEILING

GROMMET

CAT 6 MAXIMUM 6"

ACCESSIBLE CEILING

SUPPORT CABLE TO STRUCTURE

TRIM RING

CAMERA

TILE BRIDGE

NOTE: COORDINATE W/ EQUIP MANUFACTURER FOR HARDWARE AND ACCESSORIES

B

ACCESSIBLE CEILING TILE (ACT)

CAMERA IN HARD CEILING DETAIL

IP CAMERA W/ INDOOR HARDMOUNT NOTE:

5

Scale: NOT TO SCALE

COORDINATE W/ EQUIP MANUFACTURER FOR HARDWARE AND ACCESSORIES

CAMERA IN ACCESSIBLE CEILING TILE DETAIL

4

Scale: NOT TO SCALE

A

HFL 2021-2019

3

4

1

2

3

1

2

4

EXCERPT FROM W.Y. COCKEN & E.J. HERGENROEDER ARCHITECTS DRAWING NO. S-4 DATED FEB.,10, 1954 FOR REFERENCE ONLY

D

NOTES: 1. NO PENETRATIONS ARE PERMITTED IN THE 2" SECTION BETWEEN TILES.

2. WHERE FLOOR PENETRATIONS ARE MADE, A MINIMUM SPACE OF ONE (1) DIAMETER OF THE PENETRATION SHALL BE LEFT BETWEEN ADJACENT PENETRATIONS. WHERE TWO DIFFERENT DIAMETERS ARE ADJACENT, THE LARGER DIAMETER SHALL BE USED FOR THE SPACE. 3. HANGING LOADS ARE PERMITTED TO USE TOGGLE BOLTS OR ADHESIVE ANCHORS. EXPANSION ANCHORS ARE NOT PERMITTED FOR HANGING LOADS. 4. FOR FLOOR MOUNTED LOADS ADHESIVE ANCHORS OR EXPANSION ANCHORS ARE PERMITTED. 5. PRIOR TO MAKING ANY FLOOR PENETRATIONS THE CONTRACTOR SHALL USE NON-DESTRUCTIVE TESTING TO LOCATE THE #9 REINFORCING MEMBERS.

EXPOSED CEILING MOUNTED CAMERA DETAIL

1

Scale: NOT TO SCALE

J-HOOK DETAIL

C

2

Scale: NOT TO SCALE

1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU HORIZONTAL WIRE MANAGER 1 RU CISCO CATALYST 9300 1 RU OPEN 2 RU 48-PORT COPPER PATCH PANEL

45

45

44

44

43

43

42

42

41

41

40

40

39

39

38

38

37

37

36

36

35

35

34

34

33

33

32

32

31

31

30

30

29

29

28

28

27

27

B

26

26

25

25

24

24

PROVIDE AND INSTALL 48-PORT COPPER PATCH PANEL FOR TERMINATION OF THE NEW DATA CABLING FOR NEW

23

23

CAMERA'S

22

22

2 RU HORIZONTAL WIRE MANAGER

PROVIDE AND INSTALL HORIZONTAL WIRE MANAGER

ROOM #

21

21

20

20

PROVIDE AND INSTALL 48-PORT COPPER PATCH PANEL FOR TERMINATION OF THE NEW DATA CABLING FOR NEW

2 RU 48-PORT COPPER PATCH PANEL

CABINET #

MDF CABINET/LIU PANEL

19

19

OPTICAL

LABEL AFFIXED TO CABLE AND COVERED WITH CLEAR ADHESIVE TAPE. SEE LABEL FORMAT DETAIL FOR MORE

IDENTIFICATION

CAMERA'S

FIBER

PANEL #

18

18

CABLING

17

17

PORT #

INFORMATION.

16

16

15

15

21 - B1 - 01 - 100 535 - B1 - 01 -100

14

14

NOTE:

21 - B1 - 01 - 100 535 - B1 - 01 -100

13

13

U.N.O. RACK ELEVATION PROVIDED FOR REFERENCE. EXISTING EQUIPMENT WITHIN THIS RACK SHALL REMAIN.

12

12

11

11

10

10

NOTES: 1. LABELING SHALL BE ON A WHITE BACKGROUND WITH BLACK LETTERS AND COVERED WITH A CLEAR TAPE COVERING. 2. LABELS SHALL BE PLACED NO CLOSER THAN 12" AND NOT FURTHER THAN 18" FROM ENDS OF CABLE (THIS APPLIES TO BOTH ENDS OF THE CABLE).

PORT #

09

09

08

08

PANEL #

CABINET/LIU PANEL IDENTIFICATION

07

07

CABINET #

06

06

05

05

ROOM #

2 RU RACK MOUNT APC PDU ETR

04

04

03

03

2 RU RACK MOUNT APC PDU ETR

02

02

1 RU RACK MOUNT GROUNDING BUSBAR

LABEL LOCATION AND APPLICATION

LABEL FORMAT DETAIL

01

01

A

TYPICAL OPTICAL FIBER CABLE LABELING SCHEME DETAIL

RACK G08 ELEVATION

3

4

Scale: NOT TO SCALE

Scale: NOT TO SCALE

HFL 2021-2019

3

4

1

2

3

1

2

4

NOTES:

NOTES:

D

System No. W-L-1303 F Ratings - 1 and 2 Hr (See Item 1)

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Min thickness of concrete wall is 6-1/2 in. (165 mm). Wall may also be constructed of any UL Classified . Max diam of opening is 10 in. (254 mm). See Concrete Blocks (CAZT) in Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve - (Optional) - Nom 10 in. (254 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast into floor assembly. As an alternate, nom 10 in. (254 mm) diam (or smaller) sleeve fabricated from nom 0.019 in. (0.48 mm) thick galv steel cast into floor assembly flush with floor surfaces. 3. Through Penetrant - One metallic pipe or tubing to be installed concentrically or eccentrically within opening. Penetrant to be rigidly supported on both sides of floor. The following types and sizes of metallic pipe or tube may be A. Steel Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. Iron Pipe - Nom 4 in. (102 m) diam (or smaller) cast or ductile iron pipe. C. Copper Tubing - Nom 4 in. (102 mm) diam (or smaller) Type M (or heavier) copper tube. D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. 4. Pipe Covering* - Max 2 in. (51 mm) thick hollow cylindrical heavy density glass fiber units jacketed on the outside with used: B. an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt strip tape supplied with the product. The annular space between the pipe covering and the edge of the opening shall be min 1/4 in. (6 mm) to max 1-5/8 in. (41 mm). See Pipe and Equipment Covering - Materials * (BRGU) category in Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4A. PVC Jacket+ - (Not Shown) - An additional PVC jacket, supplied in sheet form, shall be tightly wrapped around the all service jacket on the pipe covering when a W Rating is required in floor assemblies. The longitudinal seam of the PVC jacket shall be continuously sealed using the adhesive supplied with the jacket. The jacket is to be nom 48 in. (1.22 m) wide by nom 20 or 30 mil (0.5 or 0.8 mm) thick. The PVC jacket shall be positioned with its top edge located 37 in. to 40 in. (0.94 to 1.02 m) above the top surface of the floor assembly and shall extend downward into and/or through the floor opening. See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability 5. Firestop System - The details of the firestop system shall be as follows: A. Packing Material - Min 2-1/2 in. (64 mm) thickness of firmly packed mineral wool batt insulation used as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall to accommodate the required thickness of fill material (Item 5B). B. Fill, Void or Cavity Material* - Sealant - Min 2 in. (51 mm) thickness of fill material applied in annular space flush with top surface of floor or with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - Pensil 300 Sealant or SpecSeal Series SIL300 Sealant for floors and walls and Classification of 94-5VA may be used.

1. Wall Assembly - The fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design. Max diam of opening is 16 in. (406 mm). Max diam of opening is 12 in. (305 mm) when wood studs are used. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.

T Rating - 1/4 Hr

A

System No. C-AJ-5312

3A

3B

F Rating - 2 Hr T Rating - 1 Hr

2. Through Penetrants - One metallic pipe, conduit or tube installed concentrically or eccentrically within the firestop system. Annular space to be min 0 in. (point contact) to max 3 in. (76 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. 3C B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.

L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft W Rating - Class 1 (See Item 4A)

A

2

5A

2

C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) electrical metallic tubing (EMT) or nom 1 in. (25 mm) diam (or smaller) flexible steel conduit. D. Copper Pipe or Tubing - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe or Type L (or heavier) copper tube. 3. Firestop System - The firestop system shall consist of the following: A. Metallic Sleeve - Cylindrical sleeve fabricated from min 0.016 in. (0.41 mm) thick (30 gauge) galv sheet steel and having a min 1 in. (25 mm) lap along the longitudinal seam. Sheet steel coiled to a diam less than circular cutouts in wall assembly, inserted through both sides of wall and allowed to uncoil against the circular cutouts in the wall assembly. Sleeve to be installed flush with or extending max 4 in. (102 mm) beyond each surface of the wall assembly. 3C A1. Metallic Sleeve - (Optional, Not Shown) - As an alternate to Item 3A, steel sleeve may consist of Schedule 5 (or heavier) steel pipe, rigid steel conduit or EMT friction-fitted into wall assembly flush with or extending 4 in. (102 mm) beyond each surface of the wall assembly. B. Packing Material - Min 2 in. (51 mm) thickness of nom 4 pcf (64 kg/m3) mineral wool batt insulation tightly-packed into ends of steel sleeve and recessed to accommodate required thickness of fill material (Item 3C). C. Fill, Void or Cavity Materials* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within annular space flush with edges of steel sleeve on both sides of the wall assembly. Nom 1/4 in. (6 mm) diam bead of fill material to be applied at the point contact location between the metallic penetrant and the steel sleeve. Additional nom 1/4 in. (6 mm) diam bead of fill material applied at the steel sleeve/gypsum board interface when sleeve projects beyond the surface of the wall assembly.

5B

A

4

1B

3

3B

3A

A

2

3

5B

4 1

2

1A

C

SPECIFIED TECHNOLOGIES INC- Pensil 300 Sealant or SpecSeal Series SIL300 Sealant

5A

Section A-A

*Bearing the UL Classification Mark

Pensil 300 S/L Sealant or SpecSeal Series SIL300SL Sealant for floors only.

Section A-A *Bearing the UL Classification Mark +Bearing the UL Recognized Component Marking R THROUGH PENETRATION - CONCRETE FLOOR/WALL METALLIC CONDUIT NO SCALE

R

THROUGH PENETRATION - GYPSUM WALL METALLIC CONDUIT NO SCALE

NOTES:

System No. C-AJ-5311

1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL ClassifiedConcrete Blocks*. Max diam of opening 6 in. (203

F Rating - 2 Hr T Rating - 1/2 Hr

mm).

L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft W Rating - Class 1

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Steel Sleeve - (Optional) - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast into floor or wall assembly. As an alternate, nom 6 in. (152 mm) diam (or smaller) sleeve fabricated from nom 0.019 in. (0.48 mm) thick galv steel cast into floor or wall assembly flush with floor or wall surfaces. 3. Through Penetrant - One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Penetrant rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipe or tubing may be used: A. Steel Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 2 in. (51 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Tubing - Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tube. D. Copper Pipe - Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe. 4. Tube Insulation - Plastics++ - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space between the insulated pipe or tube and the edge of the through opening shall be min 3/4 in. (19 mm) to max 1-5/8 in. (41 mm). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.

FIRESTOP GENERAL NOTES 1. Any pipe or conduit with a diameter smaller than the listed value may be used. 2. Any pipe or conduit with a wall thickness heavier than the listed value may be used. 3. A rated firestop system "F" rating may be applied to a wall or floor of equal or lesser "F" rating, the system then is rated at the lesser "F" rating. 4. Stencil UL number on both sides of wall above ceiling and on pipe in ceiling. 5. Stencil UL number on pipe/pipe insulation for vertical penetration. Stencil on both sides of penetration. 6. Provide STI sticker on both sides of penetration (wall or floor). Include STI detail number, wall/floor UL rating, date installed, and installing contractor. 7. UL system number to be verified in field for appropriate wall/floor system. 8. Seal unrated walls similar to firestop details 9. Seal existing pipes thru existing wall/floor that are not sealed. for bidding purposes, seal 10 pipe penetrations assuming 4" diameter pipes. (both insulated and uninsulated) 10. Fire stop material shall be as follows. Drywall penetrations shall be latex based and red in color. Floor, concrete, and exterior penetrations shall be grey in color and silicon based. Deviations shall be submitted to the engineer for review. 11. Firestop shall be products as manufactured by STI.

A

2

5A

3

5B

4

B

A

4

5B

5. Firestop System - The details of the firestop system shall be as follows:

1

A. Packing Material - Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall to accommodate the required thickness of fill material. B. Fill, Void or Cavity Materials* - Sealant - Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. A min 1/16 in. (1.6 mm) thick film of sealant shall be applied to cover edge of steel sleeve and to lap min 1/2 in. (13 mm) onto concrete around perimeter of opening. SPECIFIED TECHNOLOGIES INC- Pensil 300 Sealant or SpecSeal Series SIL300 Sealant for floors and walls and

2

5A

Pensil 300 S/L Sealant or SpecSeal Series SIL300SL Sealant for floors only.

3

*Bearing the UL Classification Mark ++Bearing the UL Recognized Component Marking

Section A-A

R THROUGH PENETRATION - CONCRETE FLOOR/WALL METALLIC CONDUIT NO SCALE

FIRE STOP DETAILS

1

Scale: NOT TO SCALE

A

HFL 2021-2019

3

4

1

2

3

1

2

4

NOTES:

1.

2

270 DEGREE CAM

D

KEYNOTES: 1.

PROVIDE AND INSTALL 3/4" CONDUIT W/

CAT6 TO CAMERA

2.

1

UPS

EXISTING TELEPHONE POLE

FINISHED GRADE

C

EXISTING TELEPHONE POLE WITH MOUNTED BOX DETAIL 2

EXISTING POLE MOUNTED HOFFMAN BOX

1

Scale: NOT TO SCALE

Scale: NOT TO SCALE

DIN RAIL CAT6 SURGE PROTECTOR ETR NEW DIN RAIL CAT6 SURGE PROTECTOR PN: WTH-SG/RJ45

#12 GROUND

NEW CAT6 OUTDOOR CABLE TO CAMERA

TWO NEW 1-1/2" PVC

120V RECEPTACLE ETR

PROVIDE AND INSTALL

EXISTING POLE MOUNTED ENCLOSURE

EXISTING UNISTRUT MOUNTED TO POLE FOR EXISTING ENCLOSURE

APC DIN RAIL - PANEL MOUNT W/ HIGH TEMP

B

CAT6 CABLE

EXISTING POLE

METAL RING CLAMP TO SUPPORT NEW HOFFMAN

PROVIDE AND INSTALL

BOX ENCLOSURE

PLUG & CORD TYP.

CISCO DC POWER SUPPLY

FIBER SPLICE

ETR

BOX ETR

FIBER SWITCH

NEW HOFFMAN BOX ENCLOSURE

ETR

AC INPUT

DC OUTPUT

NEW UNISTRUT MOUNTED TO POLE TO SUPPORT HOFFMAN BOXCLOSURE

PROVIDE 2 #12, 1 #12 GND SJO CORD

NEW POLE MOUNTED

EXISTING POLE

HOFFMAN BOX

MOUNTED ENCLOSURE

CONNECTION REFERENCE FOR OUTDOOR CAMERA

OVERHEAD POLE/ENCLOSURE MOUNTING VIEW FOR REFERENCE

4

3

Scale: NOT TO SCALE

Scale: NOT TO SCALE

A

HFL 2021-2019

3

4

1

2

3

1

2

4

D

C

EXAMPLE OF CABLE LABEL SCHEME:

NOTES: 1. VERIFY ALL LABELING WITH CCAC IT PRIOR TO PRODUCING LABELS.

SECURITY CAMERA SCHEDULE

1

Scale: NOT TO SCALE

B

A

HFL 2021-2019

3

4

1

2

3

1

2

4

BY CCAC

BY EC

D

NVR SCHEDULE

PARKING AREA CAMERA SCHEDULE

3

1

Scale: NOT TO SCALE

Scale: NOT TO SCALE

NOTES TO INDOOR CAMERA SCHEDULE 1. CONTRACTOR SHALL VERIFY ALL PART NUMBERS AND PRODUCT INFORMATION PRIOR TO ORDERING. 2. SEE RISER DIAGRAM AND PLAN SHEETS FOR ADDITIONAL INFORMATION. 3. THIS PRODUCT SET AND PART NUMBERS ARE AS MANUFACTURED BY AVIGILON, A MOTOROLA COMPANY.

BY EC

C

B

INDOOR CAMERA SCHEDULE

2

Scale: NOT TO SCALE

NOTES TO INDOOR CAMERA SCHEDULE 1. CONTRACTOR SHALL VERIFY ALL PART NUMBERS AND PRODUCT INFORMATION PRIOR TO ORDERING. 2. SEE RISER DIAGRAM AND PLAN SHEETS FOR ADDITIONAL INFORMATION. 3. THIS PRODUCT SET AND PART NUMBERS ARE AS MANUFACTURED BY AVIGILON, A MOTOROLA COMPANY. 4. SCHEDULE CONTAINS DVR PART NUMBER AS WELL AS CAMERAS.

A

HFL 2021-2019

3

4

1

2