EXCERPT FROM W.Y. COCKEN & E.J. HERGENROEDER ARCHITECTS DRAWING NO. S-4 DATED FEB.,10, 1954 FOR REFERENCE ONLY
D
NOTES: 1. NO PENETRATIONS ARE PERMITTED IN THE 2" SECTION BETWEEN TILES.
2. WHERE FLOOR PENETRATIONS ARE MADE, A MINIMUM SPACE OF ONE (1) DIAMETER OF THE PENETRATION SHALL BE LEFT BETWEEN ADJACENT PENETRATIONS. WHERE TWO DIFFERENT DIAMETERS ARE ADJACENT, THE LARGER DIAMETER SHALL BE USED FOR THE SPACE. 3. HANGING LOADS ARE PERMITTED TO USE TOGGLE BOLTS OR ADHESIVE ANCHORS. EXPANSION ANCHORS ARE NOT PERMITTED FOR HANGING LOADS. 4. FOR FLOOR MOUNTED LOADS ADHESIVE ANCHORS OR EXPANSION ANCHORS ARE PERMITTED. 5. PRIOR TO MAKING ANY FLOOR PENETRATIONS THE CONTRACTOR SHALL USE NON-DESTRUCTIVE TESTING TO LOCATE THE #9 REINFORCING MEMBERS.
EXPOSED CEILING MOUNTED CAMERA DETAIL
1
Scale: NOT TO SCALE
J-HOOK DETAIL
C
2
Scale: NOT TO SCALE
1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU 48-PORT COPPER PATCH PANEL 1 RU OPEN 1 RU CISCO CATALYST 9300 2 RU HORIZONTAL WIRE MANAGER 1 RU CISCO CATALYST 9300 1 RU OPEN 2 RU 48-PORT COPPER PATCH PANEL
45
45
44
44
43
43
42
42
41
41
40
40
39
39
38
38
37
37
36
36
35
35
34
34
33
33
32
32
31
31
30
30
29
29
28
28
27
27
B
26
26
25
25
24
24
PROVIDE AND INSTALL 48-PORT COPPER PATCH PANEL FOR TERMINATION OF THE NEW DATA CABLING FOR NEW
23
23
CAMERA'S
22
22
2 RU HORIZONTAL WIRE MANAGER
PROVIDE AND INSTALL HORIZONTAL WIRE MANAGER
ROOM #
21
21
20
20
PROVIDE AND INSTALL 48-PORT COPPER PATCH PANEL FOR TERMINATION OF THE NEW DATA CABLING FOR NEW
2 RU 48-PORT COPPER PATCH PANEL
CABINET #
MDF CABINET/LIU PANEL
19
19
OPTICAL
LABEL AFFIXED TO CABLE AND COVERED WITH CLEAR ADHESIVE TAPE. SEE LABEL FORMAT DETAIL FOR MORE
IDENTIFICATION
CAMERA'S
FIBER
PANEL #
18
18
CABLING
17
17
PORT #
INFORMATION.
16
16
15
15
21 - B1 - 01 - 100 535 - B1 - 01 -100
14
14
NOTE:
21 - B1 - 01 - 100 535 - B1 - 01 -100
13
13
U.N.O. RACK ELEVATION PROVIDED FOR REFERENCE. EXISTING EQUIPMENT WITHIN THIS RACK SHALL REMAIN.
12
12
11
11
10
10
NOTES: 1. LABELING SHALL BE ON A WHITE BACKGROUND WITH BLACK LETTERS AND COVERED WITH A CLEAR TAPE COVERING. 2. LABELS SHALL BE PLACED NO CLOSER THAN 12" AND NOT FURTHER THAN 18" FROM ENDS OF CABLE (THIS APPLIES TO BOTH ENDS OF THE CABLE).
PORT #
09
09
08
08
PANEL #
CABINET/LIU PANEL IDENTIFICATION
07
07
CABINET #
06
06
05
05
ROOM #
2 RU RACK MOUNT APC PDU ETR
04
04
03
03
2 RU RACK MOUNT APC PDU ETR
02
02
1 RU RACK MOUNT GROUNDING BUSBAR
LABEL LOCATION AND APPLICATION
LABEL FORMAT DETAIL
01
01
A
TYPICAL OPTICAL FIBER CABLE LABELING SCHEME DETAIL
RACK G08 ELEVATION
3
4
Scale: NOT TO SCALE
Scale: NOT TO SCALE
HFL 2021-2019