Bid 1101

CCAC West Hills Campus WHC Main Roof Project WHC Main Roof Project

Date of Issue (05/26/2022)

1.5

INFORMATIONAL SUBMITTALS

A. Contractor's Product Certificate: Submit certificate, indicating products intended for Work of this Section, including product names and numbers and manufacturers' names, with statement indicating that products to be provided meet the requirements of the Contract Documents. B. Qualification Data: For Installer, Manufacturer and Roofing Inspector. 1. Include letter from Manufacturer written for this Project indicating approval of Installer. C. Manufacturer Certificates: Signed by roofing manufacturer certifying that roofing system complies with requirements specified in "Performance Requirements" Article. 1. Submit evidence of compliance with performance requirements. a. Include: UL listing certificate. 2. Product Compatibility: Indicate manufacturer has verified compatibility of roofing system components, including but not limited to: Roofing membrane, flashing sheets, adhesives, and sealants.

D.

Warranties: Unexecuted sample copies of special warranties.

E. Inspection Reports: Reports of Roofing Inspector. Include weather conditions, description of work performed, tests performed, defective work observed, and corrective actions taken to correct defective work. 1.6 CLOSEOUT SUBMITTALS A. Executed copies of warranties. B. Maintenance Data: To include in maintenance manuals. 1.7 QUALITY ASSURANCE A. Installer Qualifications: An employer of workers trained and certified by manufacturer, including a full-time on-site supervisor with a minimum of five years' experience installing products comparable to those specified, able to communicate verbally with Contractor, Architect, and employees, and qualified by the manufacturer to install manufacturer's product and furnish warranty of type specified. B. Manufacturer Qualifications: Approved manufacturer listed in this Section, UL listed for roofing systems comparable to that specified for this Project, with minimum five years' experience in manufacture of thermoplastic roof membrane products in successful use in similar applications. C. Roofing Inspector Qualifications: A technical representative of manufacturer not engaged in the sale of products and experienced in the installation and maintenance of the specified roofing system, qualified to perform roofing observation and inspection specified in Field Quality Control Article, to determine Installer's compliance with the requirements of this Project, and

075419 - Page 3 of 14 POLYVINYL-CHLORIDE (PVC/TPA) ROOFING

Made with FlippingBook - Online magazine maker