Community College of Allegheny County OCS Security Camera System Pittsburgh, PA
SECTION 078443 - JOINT FIRESTOPPING
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
1.2
SUMMARY
A.
Section Includes: 1.
Joints in or between fire-resistance-rated constructions. Joints at exterior curtain-wall/floor intersections.
2. 3.
Joints in smoke barriers.
1.3
INFORMATIONAL SUBMITTALS
A.
Qualification Data: For Installer.
B. Product Test Reports: For each joint firestopping system, for tests performed by a qualified testing agency.
1.4
CLOSEOUT SUBMITTALS
A. Installer Certificates: From Installer indicating that joint firestopping systems have been installed in compliance with requirements and manufacturer's written instructions.
1.5
QUALITY ASSURANCE
A. Installer Qualifications: A firm that has been approved by FM Approvals according to FM Approvals 4991, "Approval of Firestop Contractors," or been evaluated by UL and found to comply with UL's "Qualified Firestop Contractor Program Requirements."
1.6
PROJECT CONDITIONS
A. Environmental Limitations: Do not install joint firestopping systems when ambient or substrate temperatures are outside limits permitted by joint firestopping system manufacturers or when substrates are wet due to rain, frost, condensation, or other causes.