Bid 1093 - Security Replacement Project at OCS - Invitation…

Community College of Allegheny County OCS Security Camera System Pittsburgh, PA

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use. 2. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide." D. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8 for stranded conductors. E. Conductor Insulation: 1. Type RHH and Type RHW-2: Comply with UL 44. 2. Type TC-ER: Comply with NEMA WC 70/ICEA S-95-658 and UL 1277. 3. Type THHN and Type THWN-2: Comply with UL 83. 4. Type XHHW-2: Comply with UL 44. F. Shield

2.2

METAL-CLAD CABLE, TYPE MC

A. Description: A factory assembly of one or more current-carrying insulated conductors in an overall metallic sheath. B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. AFC Cable Systems; Atkore International. 2. Alpha Wire Company. 3. Belden Inc. 4. Encore Wire Corporation. 5. General Cable; Prysmian Group North America. 6. Okonite Company (The). 7. Southwire Company, LLC. C. Standards: 1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use. 2. Comply with UL 1569. 3. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide." D. Circuits: 1. Single circuit with color-coded conductors. E. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8 for stranded conductors.

260519 - 2

Made with FlippingBook Online newsletter maker