2) 3)
Calibrated torque wrench. Thermographic survey.
c. Inspect compression-applied connectors for correct cable match and indentation. d. Inspect for correct identification. e. Inspect cable jacket and condition. f. Insulation-resistance test on each conductor for ground and adjacent conductors. Apply a potential of 500 V(dc) for 300 V rated cable and 1000 V(dc) for 600 V rated cable for a one-minute duration. g. Continuity test on each conductor and cable. h. Uniform resistance of parallel conductors.
B. Cables will be considered defective if they do not pass tests and inspections. C. Prepare test and inspection reports to record the following: 1. Procedures used. 2. Results that comply with requirements. 3.
Results that do not comply with requirements, and corrective action taken to achieve compliance with requirements.
END OF SECTION 260519