Community College of Allegheny County OCS Security Camera System Pittsburgh, PA
b. Wallplate Material: 0.060-inch thick high-impact thermoplastic (nylon) with smooth finish and color matching wiring device. c. Color: Ivory or as indicated on Drawings.
2.15 HOODS FOR OUTLET BOXES A. Performance Criteria: 1.
Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use. 2. General Characteristics: a. Reference Standards: 1) UL 514D and UL Category Control Numbers QCIT and QCMZ. 2) Receptacle, hood, cover plate, gaskets, and seals comply with UL 498 Supplement SA when mated with box or enclosure complying with UL 514A, UL 514C, or UL 50E.
b.
Mounts to box using fasteners different from wiring device.
B.
Retractable or Reattachable Hoods for Outlet Boxes: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: a. ABB, Electrification Business. b. Raco Taymac Bell; brand of Hubbell Electrical Solutions; Hubbell Incorporated. 2. Options: a. Provides clear, weatherproof, "while-in-use" cover.
PART 3 - EXECUTION
3.1
SELECTION OF RACEWAYS
A. Unless more stringent requirements are specified in Contract Documents or manufacturers' written instructions, comply with NFPA 70 for selection of raceways. Consult Engineer for resolution of conflicting requirements. B. Outdoors: 1. Exposed and Subject to Severe Physical Damage: RMC. 2. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.
260533-15