4. Comply with NECA NEIS 101 for installation of steel raceways. 5. Comply with NECA NEIS 111 for installation of nonmetallic raceways. 6. Install raceways square to the enclosure and terminate at enclosures without hubs with locknuts on both sides of enclosure wall. Install locknuts hand tight, plus one-quarter turn more. 7. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to metric designator 35 (trade size 1-1/4) and insulated throat metal bushings on metric designator 41 (trade size 1-1/2) and larger conduits terminated with locknuts. 8. Raceway Terminations at Locations Subject to Moisture or Vibration: a. Provide insulating bushings to protect conductors, including conductors smaller than No. 4 AWG. B. General Requirements for Installation of Raceways: 1. Complete raceway installation before starting conductor installation. 2. Provide stub-ups through floors with coupling threaded inside for plugs, set flush with finished floor. Plug coupling until conduit is extended above floor to final destination or a minimum of 2 ft above finished floor. 3. Install no more than equivalent of three 90-degree bends in conduit run. Support within 12 inch of changes in direction. 4. Make bends in raceway using large-radius preformed ells except for parallel bends. Field bending must be in accordance with NFPA 70 minimum radii requirements. Provide only equipment specifically designed for material and size involved. 5. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines. 6. Support conduit within 12 inch of enclosures to which attached. 7. Install raceway sealing fittings at accessible locations in accordance with NFPA 70 and fill them with listed sealing compound. For concealed raceways, install fitting in flush steel box with blank cover plate having finish similar to that of adjacent plates or surfaces. Install raceway sealing fittings in accordance with NFPA 70. 8. Install devices to seal raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal interior of raceways at the following points: a. Conduit extending from interior to exterior of building. b. Where otherwise required by NFPA 70. 9. Do not install conduits within 2 inch of the bottom side of a metal deck roof. 10. Keep raceways at least 6 inch away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping. 11. Cut conduit perpendicular to the length. For conduits metric designator 53 (trade size 2) and larger, use roll cutter or a guide to make cut straight and perpendicular to the length. Ream inside of conduit to remove burrs. 12. Install pull wires in empty raceways. Provide polypropylene or monofilament plastic line with not less than 200 lb tensile strength. Leave at least 12 inch of slack at both ends of pull wire. Cap underground raceways designated as spare above grade alongside raceways in use.

260533-17

Made with FlippingBook Online newsletter maker