Community College of Allegheny County OCS Security Camera System Pittsburgh, PA
C. Tests and Inspections: 1. Perform tests and inspections in accordance with manufacturers' instructions. D. Nonconforming Work: 1. Unit will be considered defective if it does not pass tests and inspections. 2. Remove and replace defective units and retest. E. Assemble and submit test and inspection reports. FIELD QUALITY CONTROL OF STRAIGHT-BLADE RECEPTACLES A. Testing Preparation: B. Field tests and inspections must be witnessed by Engineer. C. Tests and Inspections: 1. Insert and remove test plug to verify that device is securely mounted. 2. Verify polarity of hot and neutral pins. 3. Measure line voltage. 4. Measure percent voltage drop. 5. D. Nonconforming Work: 1. Device will be considered defective if it does not pass tests and inspections. 2. Remove and replace defective units and retest. E. Assemble and submit test and inspection reports.
3.6
Measure grounding circuit continuity; impedance must be not greater than 2 ohms.
3.7
FIELD QUALITY CONTROL OF LOCKING RECEPTACLES
A.
Testing Preparation:
B.
Field tests and inspections must be witnessed by Engineer.
C.
Tests and Inspections: 1. Insert and remove test plug to verify that device is securely mounted. 2. Verify polarity of hot and neutral pins. 3. Measure line voltage. 4. Measure percent voltage drop. 5. Measure grounding circuit continuity; impedance must be not greater than 2 ohms. 6. Perform additional installation and maintenance inspections and diagnostic tests in accordance with NECA NEIS 130 and manufacturers' instructions.
262726-8