f. Load Power Factor Range: The load power factor range shall be 0.65 lagging to 1.0 (unity) leading without power derating. g. Output Power Rating: Output power rating shall be 5000VA/5000Watts, 6000VA/6000 Watts, 8000VA/8000 Watts, 10,000VA/10,000 Watts. h. Inverter Overload Capability Overload Percent Duration Inverter shall support rated load

105% to 125% 5 minutes 125% to 150% 60 seconds >150%

Minimum of 200ms

i. Voltage Transient Response: The transient response of the output voltage with resistor step loading will be +/-5% for input supply from off to on and for a load from 0% to 100% and 100% to 0%. Transient response in the output voltage with resistor step loading will be +/-4% for input supply from off to on and for a load from 20% to 100% and 100% to 20%. j. Transient Recovery Time: To nominal voltage within 60ms. k. AC-AC Efficiency: The UPS shall be EPA Energy Star Qualified. 1) GXT5-5000MVRT4UXLN: 93% AC –AC at full rated linear load

1.5

ENVIRONMENTAL CONDITIONS

A.

Ambient Temperature 1.

Operating: The ambient temperature range, when UPS is operational, shall be from 32°F to 104°F (0°C to 40°C). There shall not be any degradation in the performance when operating in this range. Automatic derating shall occur for operation in higher ambient temperatures. 2. Storage: 5°F to 104°F (-15°C to 40°C). B. Relative Humidity 1. Operating: 0 to 95% non-condensing. 2. Storage: 0 to 95% non-condensing. C. Altitude: 10,000 ft. (3,000m) max., without power derating when operated within the temperature specified in Section 1.4, Item A. Ambient temperature shall be derated 9°F (5°C) for each additional 1600 ft. (500m) above 10,000 ft. (3,000m). D. Audible Noise: The audible noise of the UPS shall be less than 55dBA max when measured at 1 meter from front, sides, or rear.

263353-5

Made with FlippingBook Online newsletter maker