Community College of Allegheny County OCS Security Camera System Pittsburgh, PA
Frequency (Hz)
Battery
Battery status
Battery voltage (V) Battery current (A) Backup time (min)
Remaining capacity (%)
Discharge count (number of discharges for the battery module)
Total discharge time (min) Batt running time (day)
Battery replacement time (date of last replacement)
External battery cabinet group No. Battery average temp (°C)
Battery highest temp (°C) Battery lowest temp (°C)
Output
L-N voltage (V) L-N current (A) Frequency (Hz) Energy (kWh)
Load
Sout (apparent output power, kVA) Pout (active output power, kVA)
Power Factor Load Percent (%) Time Since Startup Days / Hours / Minutes
4) Settings: The UPS Configuration screens shall provide the following customizable parameters: (default values are listed first): Output Voltage selection Startup on Bypass (Enable/Disable) Frequency Selection (Auto bypass Enable/Auto bypass disable/50Hz no bypass/60Hz no bypass) Bypass voltage upper limit Bypass voltage lower limit Run mode (normal mode, or ECO mode) ECO voltage range ECO frequency range ECO requalification time Battery External Battery AH External battery cabinet group No. (0-10) Low Battery time Battery replaced time
263353-10