Community College of Allegheny County OCS Security Camera System Pittsburgh, PA
5. ANSI/TIA/EIA-607-A -- Commercial Building Grounding and Bonding Requirements for Telecommunications. 6. ANSI/TIA/EIA-758 – Customer Owned Outside Plant 7. NFPA Part 70 (NEC) 8. Install cabling in accordance with the most recent edition of BICSI publications: a. BICSI -- Telecommunications Distribution Methods Manual b. BICSI -- Cabling Installation Manual 9. Contractor Qualifications. a. Contractors must have experience installing voice and data lines using Cat 6A cabling with PAIGE DATACOM SOLUTIONS connectors. b. Contractors must be PAIGE DATACOM SOLUTIONS certified and are to include documentation from PAIGE DATACOM SOLUTIONS indicating such with the bid.
PART 2 - PRODUCTS
2.1
GENERAL
A. Voice and data lines using Cat 6A plenum cabling with PAIGE DATACOM SOLUTIONS connectors. B. Velcro is the only acceptable cable tie wrap. Location where tie wrap is acceptable is in all concealed locations. C. All cabling is to be tested with a Certification Level testing unit from a major manufacturer including Fluke and/or Ideal to verify Cat 6A compliance and documentation of these tests provided to CCAC. D. Contractor must label each new cable at the faceplate and patch panel using the CCAC adopted labeling schematic. E. All new cabling must come with a manufacturer’s 25 year warranty on all inside cabling. F. All conduit installations shall conform to the requirements of specification section Raceways and Boxes.
2.2
STANDARDS
A. The following materials must be utilized for any and all installation for this project: 1.
Cat 6a Horizontal Copper Cabling: PAIGE DATACOM SOLUTIONS GAME CHANGER UTP 600MHZ (Blue for Data; Black for security; and White for Voice).
271300 - 2
Made with FlippingBook Online newsletter maker