SEE SPECIFIC WALL TERMINATION
SPECIFIED FLASHING MEMBRANE
SPECIFIED TERMINATION BAR OR FASTENERS WITH PLATES 8" O.C.
HEAT WELDED LAPS
SPECIFIED FASTENER AND PLATE
HEAT WELDED LAP
SPECIFIED MEMBRANE
SPECIFIED ADHESIVE
ROOF DECK
INSULATION (WHERE SPECIFIED)
NOTE: 1) VERTICAL WALL FLASHING TERMINATIONS SHALL NOT EXCEED 30” WITHOUT ADDITIONAL PARALLEL HORIZONTAL ROWS OF TERMINATION BARS BETWEEN THE DECK AND THE TERMINATION POINT OF THE FLASHING. SPACING BETWEEN HORIZONTAL ROWS SHALL NOT EXCEED 24”.
SCALE:
SHEET TITLE:
NTS
PARAPET WALL FLASHING DETAIL
DRAWING No.:
11