240405-Climate Catalogue-Digital

CLIMATE CHILLED WATER SYSTEMS

Model 1 2

AU6HV

AU9HV

AU12HV

AU18HV

AU24HV

Nominal Capacity - Cool (BTU/h)

6000

9000

12000

18000

24000

Voltage @ 50/60Hz 1-Ph (V)

230

115

230

115

230

115

230

115

230

115

Full Load Amps (FLA) Cool (A)

0.83

1.56

0.61

1.14

0.78

1.61

1.18

2.52

1.64

3.4

Full Load Amps (FLA) Heat (A)

5.18

10.26

4.96

9.84

7.3

14.65

14.22 28.61

14.68

29.49

Optional Electric Heat (kW)

1

1.5

1.5

3

3

Max. Circuit Breaker (A)

10

15

10

15

10

20

15

30

20

35

Min. Circuit Ampacity (A)

6

11

6

11

8

16

15

30

16

31

Water Flow (gpm/lpm)

1.5/5.7

2.3/8.8

3/11.4

4.5/17.1

6/22.8

Air Flow (cfm/m3h)

229/390

278/473

338/575

465/791

506/860

External Static Pressure (in H2O/Pa)

0.3/74.7

0.3/74.7

0.3/74.7

0.3/74.7

0.3/74.7

Chilled Water Pressure Drop (PSI)

1.1

4.4

8

4.6

11

Max. Height (in/mm) 3

12.13/309

13.31/339

13.38/340

15.38/391

16.75/426

Max. Width (in/mm) 3

14.5/369

16.5/420

16.5/420

20.13/512

22.63/575

Max. Depth (in/mm) 3

12.56/320

13.25/337

14.25/362

15/381

15.38/391

Drain Connection Size (in/mm)

0.5/13

0.5/13

0.5/13

0.5/13

0.5/13

Drain Connection Type

FPT

FPT

FPT

FPT

FPT

Chilled Water Connection Size (in/mm)

0.5/13

0.5/13

0.5/13

0.5/13

0.5/13

Chilled Water Connection Type

FPT

FPT

FPT

FPT

FPT

Min. Supply Duct Size (in/mm)

5/127

6/153

6/153

7/178

8/204

Min. Supply Air Grille Size (sq in/sq cm)

35/226

49/317

70/452

100/646

140/904

Min. Return Air Grille Size (sq in/sq cm)

70/452

98/633

130/839

200/1291

240/1549

Net Weight (lbs/kg)

22/10

26/11.8

30/13.6

34.75/15.8

40.5/18.4

Gross Weight (lbs/kg)

29/13.15

34/15.4

39/17.7

45/20.5

53/24.0

1 Model numbers shown are for 115V units with high-velocity (HV) blowers. Add a ‘Z’ for 230V units; add ‘-FC’ for optional flow control; add ‘-L__’ or ‘-R__’ for valve position (relative to the coil) and angle of the blower; add ‘__kW’ for amount of optional electric heat in kilowatts (for ex. 1.5 kW). See DWG H3050002 for a visual explanation of valve orientation and blower angle. 2 ‘HV’ indicates high-velocity blower. 3 All dimensions ± 0.30 in/8 mm.

dometic.com

28 — DOMETIC.COM

Made with FlippingBook Ebook Creator