Technical features: • Thin Plate Pure Lead technology (TPPL) • Design life: 12+ years at 20 °C (until 80% nominal C10) • Maintenance-free (no topping up) during the whole service life • High-compression Absorbent Glass Mat (AGM) technology • Power (10 minutes) from 1978 to 5006 watt • Flame-retardant UL 94 HB or flame- retardant UL 94 V-0 version • Very low gassing due to internal gas recombination (99% efficiency)
Standards & certifications: • EUROBAT 2022 classification: >12 years – very long life • No restrictions for rail, road, sea, and air transportation (IATA, DGR clause A67) – trouble-free transportation of operational blocks • Approval: UL (Underwriters Laboratories) • Designed in accordance with IEC 60896-21/22 • Manufactured in Europe in our ISO 9001 certified production plants
Technical characteristics and data
Short circuit current
Nom. voltage
Power 10 min
Internal resistance
Type
Part number
Nominal capacity Length Width Height Weight
Terminal
"C10 1.80 Vpc 25 °C"
"C20 1.75 Vpc 25 °C"
"1.60 Vpc 25 °C"
(l)
(w)
(h)
approx. kg
V
mOhm*
A*
W/block Ah
Ah max. mm max. mm max. mm
S6V3100PP
NAPP063100HP0FA
6
2989
195
208
309
172
223
30.5
1,42
4358
F-M6
S12V2000PP
NAPP122000HP0FA
12
1978
56.4
60.8
220
172
219
21
7,29
1714
F-M6
S12V2800PP
NAPP122800HP0FA
12
2695
69.5
75.6
262
172
223
26
5,58
2251
F-M6
S12V3400PP
NAPP123400HP0FA
12
3344
92.8
99.6
309
172
223
31
4,71
2640
F-M6
S12V3800PP
NAPP123800HP0FA
12
3740
105
112
351
172
223
35.5
4,05
3044
F-M6
S12V4500PP
NAPP124500HP0FA
12
4305
120
126
351
172
275
43.6
3,80
3270
F-M6
S12V5200PP
NAPP125200HP0FA
12
5006
140
148
351
172
275
46.6
3,41
3629
F-M6
Container, terminal and torque Flame-retardant polypropylene (PP) according to UL 94 HB or flame-retardant polypropylene (PP) according to UL 94 V-0. Change H to V in the part number for UL 94 V-0 version.