Fluke CV Series ClirVu ® Infrared Windows
Compliance without compromise Safety without sacrifice Increase the safety and speed of electrical thermal imaging inspections with the Fluke ClirVu ® IR Windows Reduce the risk of arc-flash and electrocution, increase the safety of your personnel and reduce the time and cost of preventive maintenance • Save time with a quick and easy 5 minutes or less installation - One technician - One hole with standard Greenlee ® punch - Panel door does not need to be removed - Grounds instantly to metal enclosure with patent-pending AutoGround™ process - Maintains panel arc test ratings up to 63 kA when properly installed • Torture Tested™ to the highest arc blast test ratings - IEEE C37207: 63 kA Arc tested at KEMA, UL50/50E/50V, UL1558, IEC60529-1: IP67, IEC 60068, NEMA 4/12, CSA C222 NO14-13:2012, and CE • Convenience of both quick turn (CV400, CV300, CV200) or security keyed access (CV401, CV301, CV201) • Fluke IR Windows offered in three sizes 50 mm, 75 mm and 95 mm • Work permit requirements and NFPA 70E processes are significantly reduced • Full PPE is often not required so inspections are done faster and more conveniently • Lifetime replacement warranty against manufacturing defects
Quick & Easy Installation in 5 minutes or less
Fluke CV400
Fluke CV300
Fluke CV200
Specifications
CV400 CV401 CV300 CV301 CV200 CV201
Size
95 mm
75 mm
50 mm
Voltage Range
Any
NEMA Environment Type
Type 4/12 (indoor/outdoor)
AutoGround™ ClirVu ® Optic
Yes Yes
Included Accessories Hand Turn Door Latch (CV200, 300 & 400), Security Key Door Latch (CV201) and Warranty Statement Fluke IR Windows are supplied complete, assembled and ready for installation. Ordering Information FLUKE- CV200 50 mm, Infrared Window, Hand Turn Door Latch FLUKE- CV201 50 mm, Infrared Window, Security Key Door Latch
Operating temperature
-40ºC to + 232ºC and + 260ºC Intermittent EZAC & ZA-27 High Strength Zinc/ Aluminum Alloy
Body material
Ratings and testing Arc-Tested (IEEE C37207)
63 kA for 30 cycles @ 60 Hz at KEMA
UL 50V component recognition UL 50/NEMA Environmental Rating
Yes
NEMA Type 4/12
UL 1558
Yes Yes
CSA C22 2 No CSA Type Rating
Type 4 IEC 62271-100, 200:
IP rating
IP67 at TUV
Lloyds Register Vibration rating Humidity rating
Up to 11 kV marine switchgear, indoor or outdoor (offshore only)
FLUKE- CV300
75 mm, Infrared Window, Hand Turn Door Latch 75 mm, Infrared Window, Security Key Door Latch 95 mm, Infrared Window, Hand Turn Door Latch 95 mm, Infrared Window, Security Key Door Latch
IEC60068-2-6 at TUV IEC60068-2-3 at TUV
FLUKE- CV301
Install Actual mounting hole diameter required Greenlee Punch Kit = Punch/Die
11542 mm
8989 mm
6137 mm
FLUKE- CV400
742BB = 2984AV/2983AV
739BB = 1431AV/1432AV
76BB = 441AV/442AV
FLUKE- CV401
Security Key
Security Key
Security Key
Door Latch
Hand Turn
Hand Turn
Hand Turn
Optics Optic insert diameter
95 mm
75 mm
50 mm
C ontact your local distributor for price and availability. fluke.co/wtb
fluke co/infrared
Industrial Imaging
61