Fluke BT500 Series Battery Analysers
More battery tests. Less time. Fluke’s BT500 Series Battery Analysers cover a broad range of battery test functions ranging from DC voltage and resistance tests to full condition testing using an automated string function testing and the test probe integrated infrared temperature measurement system. 500 Series Battery Analysers are designed for measurements on stationary batteries of all types. • The world’s fastest battery measurements - reduce time of a typical battery measurement with 50% from 8 seconds to 4 seconds. • Unique CATIII 600V safety rating • Key measurements: Battery resistance, DC and AC voltage, DC and AC current, ripple voltage, frequency and battery temp. • Sequence measurement mode: Automatic or manual sequence testing of battery strings with automatic measurement storage including voltage, resistance and temperature (with BTL21 intelligent test probe). • Optimised user interface: Quick, guided setup ensures you’re capturing the right data every time. • Intelligent test probe set (BT520 and BT521): Integrated LCD display, infrared temperature measurement (BT521 only), verbal audio feedback and captures voltage readings and temperature logging automatically or via integrated save button • Three year warranty
Recommended Accessories
i410 AC/DC Current Clamp See page 173
BP500 Lithium-ion Battery 3000mAh
BTL10 Basic Battery Analyser Test Leads
FLUKE-BTL520ANG Angled Battery Analyser Test Probe
Fluke BT521
Fluke BT510
BTL20 Interactive Battery Analyser Test Probe
BTL21 Intelligent Test Probe
Functions
Range Resolution Accuracy
BT510
BT520* BT521*
3 mΩ
0.001 mΩ 0.01 mΩ
1% + 8
l
l
l
30 mΩ 300 mΩ 3000 mΩ
0.8% + 6 0.8% + 6 0.8% + 6 0.09% + 5 0.09% + 5 0.09% + 5 0.09% + 5
l
l
l
Battery resistance 1
0.1 mΩ
l
l
l
BT521 Intelligent Test Probes
1 mΩ
l
l
l
6 V
0.001 V 0.01 V
l
l
l
60 V
l
l
l
Included Accessories 4-Wire Test Pin (set), BTL10 Basic Test Lead (set), TL175 TwistGuard™ Test Leads with Adapter, L300 Attachable LED Flashlight (2) (BT520 and BT521 only), BTL20 Intelligent Test Probe Set with Extender (no Temperature Sensor) (BT520 only), BTL21 Intelligent Test Probe Set with Extender and Temperature Sensor (BT521 only), i410 AC/DC Current Clamp (BT521 only), BP500 Lithium-ion Battery, BC500 AC Charger, Mini- USB Cable, Shoulder Strap, Belt Strap, Magnetic Hanging Strap, FlukeView ® Battery Management Software, Soft Carrying Case, Spare Fuses (2), Battery Tags (BT520 and BT521 only). Ordering Information FLK-BT510 Basic Battery Analyser FLK-BT520 Battery Analyser FLK-BT521 Advanced Battery Analyser FLK-BT520 ANG Battery Analyser with Angled Probes FLK-BT521 ANG Battery Analyser with Angled Probes
V DC
600 V
0.1 V
l
l
l
1000 V
1 V
l
V AC (45 Hz to 500 Hz with 800 Hz filter)
600 V
0.1 V
2% + 10
l
l
l
Frequency (displayed with Vac and Aac) 2
500 Hz
0.1 Hz
0.5% + 8
l
l
l
600 mV 6000 mV
0.1 mV
3% + 20 3% + 10
AC voltage ripple (20 KHz Max)
l
l
l
1 mV
l
l
l
A DC/A AC (with accessory Fluke i410)
400 A
1 A
3.5% + 2
l
Temperature Meter mode
0°C to 60°C
1°C
2°C
l
999 records for each measurement position with time stamp Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp
Sequence mode
*BT520ANG and BT521ANG for angled probe models
Specifications Size (HxWxD) and Weight
220 mm × 103 mm × 58 mm, 850 g
Screen dimensions
77 × 56 mm
Interface
USB mini
Operating temperature
0°C to 40°C 0°C to 40°C
Lithium-ion battery charging temperature
Non-condensing (10°C), <=80% RH (at 10°C to 30°C), <=75% RH (at 30°C to 40°C)
Operating humidity
IP rating
IP40
Radio
FCC Class A
Vibration requirements Drop test requirements
MIL-PRF-28800F: Class 2
1 metre
Add 0.1 × specified accuracy for each degree C above 28°C or below 18°C
Temperature coefficients
Safety compliance 600 V CAT III 1 The measurement is based on AC injection method. The injected source signal is <100 mA, 1 kHz. 2 Trigger level V AC: 10 mV, A AC: 10 A
fluke.co/batterytesters
Battery Analysers
37
Made with FlippingBook Learn more on our blog