Fluke 1507 and 1503 Insulation Resistance Testers
These lightweight, affordable insulation testers are perfect for troubleshooting, commissioning and preventive maintenance applications. • Automatic calculation of polarisation index and dialectric absorption ratio (1507 only) • Multiple test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V (1507 only) • Remote test probe for rapid testing • Insulation test range 0.01 MΩ to 10 GΩ (1507), 0.1 MΩ to 2000 MΩ (1503) • Compare (Pass/Fail) function for repetitive tests (1507 only) • Live circuit detection prevents insulation test if voltage > 30 V is detected • Auto-discharge of capacitive voltage • AC/DC voltage: 0.1 V to 600 V • Lo ohms/Earth-bond continuity (200 mA) for checking connections and motor windings • Resistance: 0.01 Ω to 20.00 Ω • One year warranty
Recommended Accessories
TPAK Magnetic Meter Hanger See page 177
TLK289 Industrial Master Test Lead Set See page 167
TL27 Heavy Duty Test Lead Set See page 164
C116 Soft Carrying Case See page 175
Fluke 1507
Fluke 1503
C101 Hard Case See page 176
Fluke 1507/1503 Applications
Features
1503
1507
User selectable test voltages for many applications Additional test voltages 50 V, 100 V, 250 V
l
l
l
Special remote control probe for easy and safe measurements Auto-discharge of capacitive voltage for added user protection Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection Save both time and money with Automatic calculation of Polarisation Index and Dielectric Absorption Ratio
l
l
l
l
Insulation test at a distribution panel
l
l
l
Auto Power off to save batteries Large display with backlight Continuity function (200 mA)
l
l
l
l
l
l
Compare function (pass/fail) for fast repetitive tests
l
Insulation
1503
1507
Wiring test in a small distribution box – all in one spot
Insulation test range
0.1 MΩ to 2000 MΩ
0.01 MΩ to 10 GΩ
Test voltages
500 V, 1000 V + 20%, - 0% 1 mA nominal
50 V, 100 V, 250 V, 500 V, 1000 V
Test voltage accuracy Insulation test current
+ 20%, - 0% 1 mA nominal
AC/DC Voltage measurement Resistance measurement range
600 V (0.1 V resolution)
600 V (0.1 V resolution)
0.01 Ω to 20 kΩ
0.01 Ω to 20 kΩ
Auto discharge
Discharge time < 0.5 second for C = 1 µF or less
Discharge time < 0.5 second for C = 1 µF or less
Maximum capacitive load Open circuit test voltage
Up to 1 µF
Up to 1 µF
> 4 V , < 8 V
> 4 V , < 8 V
Included Accessories TL224 Test Leads, TP74 Test Probes, Clips PN 1958654 (red) and PN 1958646 (black), Holster, Remote Probe and User Manual. Ordering Information FLUKE-1507 Insulation Tester FLUKE-1503 Insulation Tester
Short circuit current
> 200 mA
> 200 mA
General Battery life
Meter: 1000 hours Insulation Test: >1000 tests 203 mm × 100 mm × 50 mm
Size (HxWxD)
Weight
0.55 kg
C ontact your local distributor for price and availability. fluke.co/wtb