Shock Relay Catalog

TSBSC - BASIC WIRING SCHEMATIC

Basic wiring schematic

T ( L3 ) S ( L2 ) R ( L1 ) Power supply

CB

OCR

MC

M

Motor

Single-phase motor

OCR

MC

F

CT

M Motor

TR

Shock Relay TSBSC Series

CT

Shock Relay TSBSC Series

A1 A2

OC

OCR

STOP RUN MC

95

96

MC

RUN

CT: Current transformer CB: Circuit breaker MC: Magnetic contactor F: Fuse TR: Transformer OCR: Over current relay PL: Trip light

98

PL

TRIP

08

AL/UC /TO

Fail Safe mode :OFF ( FS:off )

+ ー

4-20 mA OUTPUT

RS485 Communication

TSBSC

Notes: 1) If necessary, set the stepdown transformer (TR) depending on the voltage on the Shock Relay and electromagnetic contactor (MC). Install an isolating transformer if there is any harmonic noise generating device, such as an inverter. 2) Output relay; Normal condition: not excited, Trip condition: excited 3) Coil capacity of MC connected to the output relay of the Shock Relay is: Throw = less than 200VA Hold = less than 20VA In the event that an auxiliary relay is used, have the output relay of the Shock Relay activate the Auxiliary Relay and have the Auxiliary Relay open/close the MC.

Connection with signal converter

1) Prepare a signal converter to use the monitoring software (PCON) of TSBSC. 2) Use twisted cables and connect as follows.

Terminal

Signal

RS485 Terminal

COMM

V-

GND

GND

D1

Data (B)

Tx+

V- D1 D0 S

D0

Data (A)

Tx-

S

Shield

Shield