TSBSB SERIES - SHOCK RELAY

MON lamp The lamp lights during normal monitoring conditions. When the shock time exceeds the preset time, the lamp turns off.

CT (current transformer)

OC lamp When the motor current

exceeds preset current value, the lamp flickers. When shock time exceeds the preset time, the lamp lights.

3

Test

1

Load Current

4

Reset

2

Start time (Setting range of 0.2-30s)

5

Shock time

(Setting range of 0.2-10s)

Control interface LOAD CURRENT

1

Load current can be set to stop the motor at the desired level when overload occurs. When the motor current exceeds the preset CURRENT value (at the same time, overload time continues to exceed the preset SHOCK TIME), the Shock Relay activates and stops the motor. START TIME When the motor starts there is a possibility that the motor current will exceed the set current value. To prevent the Shock Relay from tripping due to the spike in start current, start time is set a little bit longer than the period of motor start-up to ignore the spike. TEST Button Shock Relay operation can be tested stand-alone or during motor operation. (When testing the Shock Relay, continue to press and hold the TEST button longer than the set START TIME or SHOCK TIME, whichever is longer.) RESET Button After the Shock Relay activates, the RESET button is used to cancel the self-holding of the output contact. SHOCK TIME Shock time is the amount of time set until the Shock Relay will activate when overload occurs. Within the set time, the Shock Relay will not activate, even if it is overloaded.