Specification Product Specications Specications CPU
PR-18DC-DA-RT
Item
PR-18AC-R
PR-18DC-DA-R
Relay
Transistor
Output No
6 (Q1-Q6)
4 (Q1-Q4) Relay output 2 (Q5-Q6) Transistor output
Output type
Relay output
Continuous current Max breaking voltage Max allowable power force Electrical durability expectancy Mechanical life Voltage drop Galvanic isolation Max breaking current
Resistive load 10A/Inductive load 2A
Max. 0.3 A per channel
AC 250 V DC 110 V
DC 5-30V
10A
0.65A
-
< 2 V for I = 0.3 A (at state 1)
-
Yes
1250VA 300W
-
-
105 Operations at Rated Resistive Load
-
107 Operations at No Load condition
Against short-circuits: None Against overvoltages and overloads: None
Built-in protections
Response time
Operate Time : 15 ms max Release Time : 10 ms max
Make ≤ 1 ms Release ≤ 1 ms
Mechanism
10Hz
-
2Hz
10Hz
Resistor/light load
Sensitive load
0.5Hz
10kHz Q5, Q6 must have same frequency when PWM works
-
PWM frequency
- -
PWM accuracy at 120Hz PWM accuracy at 500Hz Max. Breaking current PWM Max. cable length PWM PWM cyclic ratio
< 0.5 % (20 % - 80 %) load at 10 mA < 0.5% (20 % - 80 %) load at 10 mA
-
50mA
- -
20m 0 to 100 %