PLC & HMI RIEVTECH ZONA INDUSTRIAL SPA

Specification Product Specications Specications CPU

PR-24DC-DAI-RTA

Item

PR-24AC-R

PR-24DC-DA-R

Relay

Transistor

Output No

10 (Q1-QA)

9 (Q1-Q8, AQ9)

6 (Q1-Q6) Relay output 2 (Q7-Q8) Transistor PNP output 1 (AQ9) Analog output (0-10/0-20mA)

Output type

Relay output

Continuous current Max breaking voltage Max allowable power force Electrical durability expectancy Mechanical life Voltage drop Galvanic isolation Max breaking current

Resistive load 10A/Inductive load 2A

Max. 0.3 A per channel

AC 250 V DC 110 V

DC 5-30V

10A

0.65A

-

< 2 V for I = 0.3 A (at state 1)

- -

Yes

1250VA 300W

- -

105 Operations at Rated Resistive Load

107 Operations at No Load condition

Against short-circuits: None Against overvoltages and overloads: None

Built-in protections

Response time

Operate Time : 15 ms max Release Time : 10 ms max

Make ≤ 1 ms Release ≤ 1 ms

-

Mechanism

10Hz

2Hz

10Hz

Resistor/light load

Sensitive load

0.5Hz

10kHz Q7, Q8 must have same frequency when PWM works

-

PWM frequency

- - - - -

PWM accuracy at 120Hz PWM accuracy at 500Hz Max. Breaking current PWM Max. cable length PWM PWM cyclic ratio Output signal Internal value and signal relationship Resolution Accuracy at 25 °C Output signal Internal value and signal relationship Resolution Accuracy at 25 °C

< 0.5 % (20 % - 80 %) load at 10 mA < 0.5% (20 % - 80 %) load at 10 mA

50mA

20m 0 to 100 %

- - - - - - - -

DC 0…10V AQ9 (0..1000) = V1(0...10V)

0.01V 0.02V

0..20mA AQ9 (0..1000) = I1(0...20mA)

0.02mA 0.05mA

Made with FlippingBook - Online magazine maker