PT100 Inputs Using the extension module It can be connected with one two-wire or three-wire Resistance Temperature Detector (RTD) PT100. The RTD sensor is comprised of a resistor that changes value with temperature. The most common RTD by far is the PT100 385. This element measures 100 Ohms @ 0 degrees C (32 °F) and 138.5 Ohms @ 100 °C (212.0 °F). The temperature range for a PT100 inputs is within -50 to 200 °C (resolution 0.3 °C).

Using a two-wire connection the unit can not compensate error/ tolerance caused by the resistance in measurement loop. The measurement error of 1Ω is equivalent to an error of 2.5 °C. The three-wire technology can inhibit the influence of measurement results caused by cable length (ohmic resistance).