SINGLE CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –1 CU or AL/XLPE/AWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, AL-WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
50 70 95
1.0 1.1
0.8 0.8
0.9
1.5 1.5
18.0 20.0
625 885
340 475
1000 1000
1.25
1.1
0.8
1.25
1.6
22.0
1160
590
1000
120 150 185 240 300 400 500 630 800
1.2
0.8
1.25
1.6
23.0
1415
695
1000
1.4
1.0
1.6
1.7
26.0
1790
900
1000
1.6
1.0
1.6
1.8
28.0
2180
1070
1000
1.7
1.0
1.6
1.8
31.0
2760
1300
1000
1.8
1.0
1.6
1.9
34.0
3375
1540
500
2.0
1.2
2.0
2.0
38.0
4370
2010
500
2.2
1.2
2.0
2.1
42.0
5400
2435
500
2.4
1.2
2.0
2.2
46.0
6915
3020
500
2.6
1.4
2.5
2.4
52.0
9030
3935
500
1000
2.8
1.4
2.5
2.5
57.0
11015
4730
500
TABLE –2
CU or AL/XLPE/PVC – IEC 60502 PART 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm
mm
kg/km
kg/km
mtrs
1.5 2.5
0.7 0.7
1.4 1.4
6.0 6.5
50 60
-- --
1000 1000
4 6
0.7
1.4
7.0
80
--
1000
0.7
1.4
7.5
100
--
1000
10 16 25 35 50 70 95
0.7
1.4
8.5
145
--
1000
0.7
1.4
9.0
200
105
1000
0.9
1.4
11.0
300
145
1000
0.9
1.4
12.0
395
180
1000
1.0
1.4
13.0
515
230
1000
1.1
1.4
15.0
715
305
1000
1.1
1.5
17.0
970
400
1000
120 150 185 240 300 400 500 630 800
1.2
1.5
19.0
1205
490
1000
1.4
1.6
21.0
1485
595
1000
1.6
1.6
23.0
1845
735
1000
1.7
1.7
26.0
2395
935
1000
1.8
1.8
28.0
2980
1145
1000
2.0
1.9
32.0
3795
1440
500
2.2
2.0
35.0
4765
1800
500
2.4
2.2
40.0
6230
2335
500
2.6 2.8
2.3 2.4
44.0 49.0
8020 9905
2920 3620
500 500
1000
11 MKK XXS002-02/01-12-2014