3 1/2 CORE (4 CORE WITH REDUCED NEUTRAL) CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –9 CU or AL/XLPE/SWA/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Area of Conductor
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
Phase Neutral Phase Neutral mm² mm
mm mm mm mm kg/km kg/km mtrs
25
16 0.9 0.7
1.0
1.6
1.8
26.0
1745
1190
1000
35
16 0.9 0.7
1.0
1.6
1.8
29.0
2105
1370
1000
50
25 1.0 0.9
1.0
1.6
1.9
31.0
2645
1630
1000
70
35 1.1 0.9
1.2
2.0
2.1
37.0
3805
2350
500
95
50 1.1 1.0
1.2
2.0
2.2
40.0
4840
2830
500
120
70 1.2 1.1
1.2
2.0
2.4
46.0
6015
3425
500
150
70 1.4 1.1
1.4
2.5
2.5
51.0
7500
4395
500
185
95 1.6 1.1
1.4
2.5
2.7
57.0
9165
5230
500
240
120 1.7 1.2
1.6
2.5
2.9
63.0
11425
6280
250
300
150 1.8 1.4
1.6
2.5
3.0
68.0
13745
7285
250
400
185 2.0 1.6
1.6
3.15
3.3
77.0
17950
9690
250
TABLE –10
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Area of Conductor
Nominal Thickness of Insulation
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
Phase Neutral
Phase Neutral
mm²
mm
mm
mm
kg/km
kg/km
mtrs
25
16
0.9
0.7
1.8
21.0
1075
515
1000
35
16
0.9
0.7
1.8
24.0
1360
625
1000
50
25
1.0
0.9
1.8
26.0
1810
800
1000
70
35
1.1
0.9
1.9
30.0
2535
1085
1000
95
50
1.1
1.0
2.1
34.0
3445
1430
500
120
70
1.2
1.1
2.2
39.0
4395
1805
500
150
70
1.4
1.1
2.3
43.0
5245
2140
500
185
95
1.6
1.1
2.5
49.0
6635
2700
500
240
120
1.7
1.2
2.7
54.0
8595
3445
500
300
150
1.8
1.4
2.9
60.0
10670
4205
500
400
185
2.0
1.6
3.1
68.0
13550
5290
250
15 MKK XXS002-02/01-12-2014
Made with FlippingBook Annual report