5 CORE CABLES - 600/1000 V DIMENSIONS & WEIGHTS TABLE –11 CU or AL/XLPE/SWA/PVC – BS 5467 CU or AL CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
1.5 2.5
0.6 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1
0.8 0.8 0.8 0.8 0.8 1.0 1.0 1.0 1.2 1.2
0.9 0.9 0.9
1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.2
15.0 16.0 18.0 20.0 23.0 26.0 30.0 33.0 38.0 43.0
380 460 580 845
-- -- -- -- --
1000 1000 1000 1000 1000 1000 1000
4 6
1.25 1.25
10 16 25 35 50 70
1125 1640 2285 2865 3935 5240
1.6 1.6 1.6 2.0 2.0
1150 1510 1790 2495 3150
500 500 500
TABLE –12
CU or AL/XLPE/PVC – IEC-60502 Part 1 CU or AL CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm
mm
kg/km
kg/km
mtrs
1.5
0.7
1.8
12.0
200
--
1000
2.5
0.7
1.8
13.0
265
--
1000
4
0.7
1.8
15.0
355
--
1000
6
0.7
1.8
16.0
475
--
1000
10
0.7
1.8
19.0
700
--
1000
16
0.7
1.8
21.0
985
495
1000
25
0.9
1.8
25.0
1500
725
1000
35
0.9
1.8
28.0
1975
900
1000
50
1.0
2.0
32.0
2645
1200
500
70
1.1
2.1
37.0
3725
1640
500
16 MKK XXS002-02/01-12-2014