CONTROL/AUXILIARY CABLES - 600/1000 V DIMENSIONS & WEIGHTS - SIZE 2.5 mm2 (Stranded) TABLE –31 CU/XLPE/SWA/PVC – BS 5467 CU CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Thickness of Insulation
Nominal Thickness of Extruded Bedding
Nominal Diameter of Armour Wire
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm mm mm mm mm kg/km kg/km mtrs
6
0.7
0.8
0.9
1.4
17.5
515
1000
1000
7
0.7
0.8
0.9
1.4
17.5
540
1000
1000
9
0.7
0.8
1.25
1.6
20.0
795
1000
1000
12
0.7
0.8
1.25
1.6
21.5
930
1000
1000
19
0.7
1.0
1.6
1.7
26.0
1415
1000
1000
21
0.7
1.0
1.6
1.8
27.0
1525
1000
1000
27
0.7
1.0
1.6
1.8
30.0
1815
1000
1000
37
0.7
1.0
1.6
1.8
33.0
2225
500
1000
48
0.7
1.2
2
2.0
38.5
3040
500
1000
DIMENSIONS & WEIGHTS - SIZE 2.5 mm2 (Stranded) TABLE –32 CU/XLPE/PVC – IEC-60502 Part 1 CU CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Thickness of Outer Sheath
Approx. Cable
Approx. Cable Weight for AL Cable
Nominal Area of Conductor
Nominal Thickness of Insulation
Approx. Overall Diameter
Packing Length (Standard)
Weight for CU Cable
mm²
mm
mm
mm
kg/km
kg/km
mtrs
6
0.7
1.8
14.0
305
1000
1000
7
0.7
1.8
14.0
325
1000
1000
9
0.7
1.8
17.0
420
1000
1000
12
0.7
1.8
18.0
510
1000
1000
19
0.7
1.8
21.0
740
1000
1000
21
0.7
1.8
22.0
815
1000
1000
27
0.7
1.8
25.0
1010
1000
1000
37
0.7
1.8
28.0
1330
1000
1000
48
0.7
1.9
32.0
1700
500
1000
28 MKK XXS002-02/01-12-2014
Made with FlippingBook Annual report