Oman Low-Voltage-Power-and-Control-Cables

CONTROL/AUXILIARY CABLES - 600/1000 V DIMENSIONS & WEIGHTS - SIZE 2.5 mm2 (Stranded) TABLE –37 CU/PVC/SWA/PVC – BS 6346 CU CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED

Nominal Thickness of Insulation

Nominal Thickness of Extruded Bedding

Nominal Diameter of Armour Wire

Nominal Thickness of Outer Sheath

Nominal Area of Conductor

Approx. Overall Diameter

Approx. Cable Weight

Packing Length (Standard)

mm²

mm

mm

mm

mm

mm kg/km mtrs

6

0.7

0.8

1.25

1.5

19.0

670

1000

7

0.7

0.8

1.25

1.5

19.0

700

1000

9

0.7

0.8

1.25

1.6

21.5

890

1000

12

0.7

0.8

1.25

1.6

23.5

1030

1000

19

0.7

1.0

1.6

1.7

28.0

1575

1000

21

0.7

1.0

1.6

1.8

29.0

1700

1000

27

0.7

1.0

1.6

1.8

32.0

2025

1000

37

0.7

1.0

1.6

1.9

35.5

2525

500

48

0.7

1.2

2.0

2.1

41.0

3445

500

DIMENSIONS & WEIGHTS - SIZE 2.5 mm2 (Stranded) TABLE –38 CU/PVC/PVC – IEC-60502 Part 1 COPPER CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)

Nominal Thickness of Outer Sheath

Approx. Cable

Approx. Cable Weight for AL Cable

Nominal Area of Conductor

Nominal Thickness of Insulation

Approx. Overall Diameter

Packing Length (Standard)

Weight for CU Cable

mm²

mm

mm

mm

kg/km

kg/km

mtrs

6

0.8

1.8

15.5

345

1000

1000

7

0.8

1.8

15.5

375

1000

1000

9

0.8

1.8

18.0

495

1000

1000

12

0.8

1.8

20.0

590

1000

1000

19

0.8

1.8

23.0

865

1000

1000

21

0.8

1.8

24.0

955

1000

1000

27

0.8

1.8

27.0

1185

1000

1000

37

0.8

1.9

30.5

1575

1000

1000

48

0.8

2.0

34.5

2020

500

1000

32 MKK XXS002-02/01-12-2014

Made with FlippingBook Annual report