Oman Low-Voltage-Power-and-Control-Cables

TABLE - 43

CURRENT RATINGS & VOLTAGE DROP OF THE CABLES - 600/1000 V 3 and 4 Core, Copper, XLPE insulated Armoured/Unarmoured Cables.

Approx Voltage Drop (3 Phase System)

Area

In Air

In Ground

In Duct

Unarmoured Armoured

Armoured

Armoured

Trefoil

mm²

A

A

A

A

V/A/km

1.5

19

20

28

22

26.73

2.5

27

27

36

29

16.37

4

34

37

47

39

10.19

6

44

46

59

48

6.81

10

58

64

79

65

4.04

16

83

83

102

83

2.55

25

105

109

131

107

1.61

35

129

134

157

128

1.17

50

157

163

187

152

0.866

70

200

205

229

187

0.608

95

246

253

274

226

0.447

120

288

293

312

258

0.363

150

330

335

349

291

0.305

185

381

386

394

329

0.256

240

454

456

455

380

0.212

300

524

519

509

427

0.187

400

608

597

574

490

0.167

Operating Conditions Ambient air temp.

50 °C 35 °C

Ground temp. Depth of Laying

0.50 m

Thermal resistivity of Soil

1.2 K.m/W