Oman Low-Voltage-Power-and-Control-Cables

TABLE - 49

CURRENT RATINGS & VOLTAGE DROP OF THE CABLES - 600/1000 V 3 and 4 Core, Copper, PVC insulated Armoured/Unarmoured Cables.

Approx Voltage Drop (3 Phase System)

Area

In Air

In Ground

I n Duct

Unarmoured Armoured

Armoured

Armoured

Trefoil

mm²

A

A

A

A

V/A/km

1.5

14

14

22

18

25.1

2.5

20

19

28

23

15.4

4

25

25

38

30

9.6

6

32

32

47

38

6.4

10

42

44

62

51

3.8

16

56

58

81

66

2.4

25

74

78

106

86

1.5

35

91

95

127

103

1.10

50

111

115

150

122

0.816

70

141

146

186

152

0.573

95

174

180

223

182

0.423

120

202

208

254

208

0.346

150

231

238

284

234

0.292

185

267

273

321

265

0.246

240

318

322

370

306

0.207

300

365

366

414

342

0.184

400

423

420

464

392

0.166

Operating Conditions Ambient air temp.

50 °C 35 °C

Ground temp. Depth of Laying

0.50 m

Thermal resistivity of Soil

1.2 K.m/W

42 MKK XXS002-02/01-12-2014