TABLE - 52
CURRENT RATINGS & VOLTAGE DROP OF THE CABLES - 600/1000 V 3 and 4 Core, Aluminium, PVC insulated Armoured/Unarmoured Cables.
Approx Voltage Drop (3 Phase System)
Area
In Air
In Ground
I n Duct
Unarmoured Armoured
Armoured
Armoured
Trefoil
mm²
A
A
A
A
V/A/km
16
42
44
62
50
4.0
25
56
57
80
65
2.5
35
68
70
96
78
1.8
50
83
86
114
93
1.3
70
106
108
141
115
0.934
95
131
134
170
139
0.681
120
151
155
194
159
0.544
150
174
177
218
178
0.450
185
200
205
247
203
0.368
240
239
245
288
238
0.294
300
276
282
326
270
0.249
400
308
308
353
286
0.210
Operating Conditions Ambient air temp.
50 °C 35 °C
Ground temp. Depth of Laying
0.50 m
Thermal resistivity of Soil
1.2 K.m/W
45 MKK XXS002-02/01-12-2014