Oman Low-Voltage-Power-and-Control-Cables

TABLE - 53

RATING FACTORS FOR VARIATION IN AMBIENT TEMPERATURE FOR CABLES LAID IN AIR (FOR INSTALLATION IN AIR ONLY)

Ambient temperature ° C 25

30

35

40

45

50

55

PVC insulated cables

1.49

1˙.40

1.31

1.22

1.11

1.00

0.86

XLPE insulated cables

1.28

1.23

1.18

1.13

1.06

1.00

0.94

TABLE - 54

RATING FACTORS FOR VARIATION IN AMBIENT TEMPERATURE FOR CABLES LAID DIRECT IN GROUND OR IN DUCTS (FOR INSTALLATION IN GROUND & DUCTS ONLY)

Ground temperature ° C 15

20

25

30

35

40

45

PVC insulated cables

1.25

1.19

1.12

1.06

1.00

0.92

0.85

XLPE insulated cables

1.16

1.13

1.08

1.03

1.00

0.95

0.90

TABLE - 55

RATING FACTORS FOR DEPTH OF LAYING FOR CABLES LAID DIRECT IN GROUND OR IN DUCTS (FOR INSTALLATION IN GROUND & DUCTS ONLY)

Cables Laid Direct in Ground

Cables Laid in Ducts

"Depth of Laying

70 mm² to 300mm2

Upto 50mm2

Above 300 mm2 Single Core

Multicore

Metre

0.75

0.975

0.965

0.947

0.957

0.982

0.8

0.970

0.960

0.940

0.950

0.980

1.0

0.950

0.930

0.920

0.930

0.960

1.25

0.940

0.920

0.890

0.910

0.950

1.5

0.930

0.900

0.870

0.890

0.940

1.75

0.920

0.890

0.860

0.880

0.940

2.0

0.910

0.880

0.850

0.870

0.930

2.5

0.900

0.870

0.840

0.860

0.920

3 or more

0.890

0.850

0.820

0.850

0.910

46 MKK XXS002-02/01-12-2014