Oman Low-Voltage-Power-and-Control-Cables

TABLE - 65

(FOR INSTALLATION IN AIR ONLY) GROUP RATING FACTORS FOR GROUPS OF MORE THAN ONE CIRCUIT OF SINGLE CORE CABLES TO BE APPLIED TO THE CURRENT-CARRYING CAPACITY FOR ONE CIRCUIT OF SINGLE-CORE CABLES IN FREE AIR

Use as a multiplier to rating for

Number of three-phase circuits (Note 3)

Number of trays

Method of Installation

1

2

3

1

1.00

0.98

0.96

Perforated trays

2

0.97

0.93

0.89

3

0.96

0.92

0.86

(Note 1)

Spaced

Vertical perforated trays (Note 2)

1

1.00

0.91

0.89

Three cables in trefoil formation

2

1.00

0.90

0.86

Ladder supports, cleats, etc. (Note 1)

1

1.00

1.00

1.00

2

0.97

0.95

0.93

3

0.96

0.94

0.90

Note 1: Values are given for vertical spacings between trays of 300 mm. For closer spacing, the factors should be reduced. Note 2: Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing, the factors should be reduced. Note 3: For circuits having more than one cable in parallel per phase, each three phase set of conductors should be considered as a circuit for the purpose of this table.