Oman Low-Voltage-Power-and-Control-Cables

TABLE - 68

A.C. RESISTANCE AND REACTANCE VALUES FOR XLPE INSULATED CABLES

XLPE Insulated Cables (600/1000 V Grade)

Nominal Cross- sectional area of conductor

A.C Resistance at 90 °C

Reactance at 50 Hz

Single Core Cables

Multi Core Cables

Single Core Cables

Multi Core Cables

Copper

Aluminium Copper

Aluminium Armoured Unarmoured

mm²

Ohm/km

Ohm/km

Ohm/km

Ohm/km

1.5

15.43

-------

15.43

-------

-------

0.147

0.105

2.5

9.45

-------

9.45

-------

-------

0.137

0.099

4

5.88

-------

5.88

-------

-------

0.128

0.093

6

3.93

-------

3.93

-------

-------

0.119

0.089

10

2.33

-------

2.33

-------

-------

0.111

0.084

16

1.47

2.45

1.47

2.45

-------

0.103

0.081

25

0.927

1.54

0.927

1.54

-------

0.103

0.081

35

0.668

1.11

0.669

1.11

-------

0.098

0.079

50

0. 494

0.822

0.494

0.822

0.114

0.093

0.078

70

0.342

0.568

0.343

0.569

0.106

0.088

0.074

95

0.247

0.411

0.248

0.411

0.102

0.086

0.072

120

0.196

0.325

0.197

0.326

0.097

0.085

0.072

150

0.160

0.265

0.160

0.265

0.099

0.085

0.073

185

0.128

0.212

0.129

0.212

0.095

0.083

0.072

240

0.0990

0.162

0.100

0.163

0.093

0.082

0.071

300

0.0805

0.130

0.0815

0.131

0.092

0.079

0.071

400

0.0645

0.102

0.0660

0.103

0.090

0.080

0.070

500

0.0525

0.0815

-------

-------

0.089

0.078

-------

630

0.0430

0.0650

-------

-------

0.087

0.078

-------

800

0.0365

0.0530

-------

-------

0.086

0.076

-------

1000

0.0320

0.0445

-------

-------

0.085

0.075

-------

54 MKK XXS002-02/01-12-2014