HHM
HHBM-BR
High Voltage Current-Limiting Fuses
BS 2692-1 IEC 606644 IEC 60282-1 Standard(s) DIN 43 625
3.6kV- Rated Voltage[U n ]
Motor Applications
Class
Back-Up
"L"=254mm
Rated
I 2 t @ Total
Rated current
Diameter Weight
current I 3 breaking Minimum
Pre-arcing
Cold
Power
D
loss
resistance
current I 1 breaking
I 2 t
0.87U n
I n
[A 2 s]
[A 2 s]
[A 2 s]
[in/mm]
[W]
[A]
[kA]
[A]
Article Number
[kg/1]
Single Barrel - With 80N Striker
20 400 9 000 5 400 62 200 37 600 170 000 100 000
3045655.2R
50 50 50 50 50 50 50
70
24 000 63
3.00 / 76 3.1 3.00 / 76 3.1 3.00 / 76 3.1
123 125 112 106 118
150 3045655.5R 130 3045655.4R 100 3045655.3R
91 500 41 400
169 000 119
3.00 / 76 3.00 / 76 3.00 / 76 3.00 / 76
3.1 3.1 3.1 3.1
3045655.12R 3045655.9R 3045655.6R
200 170 230
280 000 462 000 764 000
Double Barrel - With 80N Striker
390
3045755.18R
1 850 000 3 053 000
3.00 / 76 3.00 / 76
50 50
236 246
6.2 6.2
678 000 402 000
450 3045755.24R
Triple Barrel - With 80N Striker
12 477 000 6 869 000
3045855.36R 3045855.48R
3.00 / 76 9.3
50 50
2 776 000 1 527 000
700 650
354 476
9.3
3.00 / 76
Contact SIBA
Available for large quantities only
13mm / 0.51”
42.5mm / 1.67”
40.0mm / 1.57”
8mm / 0.31”
73mm / 3.00”
254mm / 10.00”
portal: www.siballc.net e-mail: info@sibafuse.com
121